Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 249

Advertising
background image

9-16

IM 04L31A01-17E

Executing the Auto Setting
(Applicable only to UT Series.)

8.

Use the arrow keys to move the cursor to the [Auto setting] box.

9.

Press the [Execute] soft key.
The register addresses of the connecting model are set automatically.

The register addresses are set automatically according to the various information that was
read automatically on the External loop setting (Basic setting) display.)

Note

The [Execute] soft key is used read the register addresses of the connecting model
automatically. Use caution because all preexisting register addresses will be overwritten.

Setting (Correcting) Register Addresses
(Perform the following procedures only if addresses need to be corrected.)

10.

Enter the register address of each item according to the selected connecting
model (see section 9.4).

Confirming or Canceling the Settings

11.

To confirm the new settings, press the DISP/ENTER key. To cancel the
settings, press the ESC key.

For a detailed procedure in confirming or canceling settings, see “Setup Procedure Using
Operation Keys” on page ix.

Saving the Settings

12.

Press the ESC key several times to display the basic setting menu.

13.

Press the [End] soft key. A dialog box appears for you to select whether to save
the settings.

15.

To save the settings, select [Yes]. To not save the settings, select [No]. To
return to the basic setting menu, select [Cancel]. Then, press the DISP/ENTER
key.

Note

To activate the settings that have been changed in the basic setting mode, the settings must be
saved. Otherwise, the settings that existed before the change are activated.

9.5 External Loop Setting > Parameter Address Setting