5 setting commands (measurement), Setting commands (measurement) -27, Sr sets the input range – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 156

Advertising
background image

6-27

IM 04L31A01-17E

6

Command

RL:

Select remote/local

0: Local operation

1: Remote operation (cannot be

selected in the following cases.

UT420/UT450/UT520/UT550:

control mode is single loop and no

control hold function

UT750: control mode is cascade

secondary

Not available with UT320/UT321/

UT350/UT351

SR:

Operation start/stop

0: Operation start

1: Operation start

Not available depending on the UT

operation mode

MOUT: Changing the control output value

(available during manual operation)

During On/off control: 0.0%,

100.0%

When other than onoff control:

-5.0% to 105.0%

SPN:

Switching the target setpoint

number

1: Select target setpoint number 1

:

8: Select target setpoint number 8

For UT320/UT321/UT350/UT351,

can select 1–4

Example

Run external loop 2 automatically.

DV2,MODE,0

6.5 Setting Commands (Measurement)

6.5

Setting Commands
(Measurement)

SR

Sets the input range

When setting channels to skip

Syntax

SR p1,p2<terminator>
p1: Channel number (01 to 20) (01 to 06 on the

CX1000)

p2: Range mode (SKIP)

Query

SR[ p1]?

Example

Set channel 01 to skip.

SR01,SKIP

Description • This command cannot be specified while

measurement/computation is in progress or

while a report is being created.

• Measurements are not made on channels that

are set to SKIP.

When setting the channels to voltage, TC, RTD, or
ON/OFF input

Syntax

SR p1,p2,p3,p4,p5<terminator>
p1: Channel number (01 to 20) (01 to 06 on the

CX1000)

p2: Input type

VOLT

DC voltage

TC

TC

RTD

RTD

DI ON/OFF input

p3: Measurement range

p4: Span lower limit

p5: Span upper limit

Query

SR[ p1]?

Example

Set the input type for channel 01 to TC type R,

span lower limit to 0°C, and span upper limit to
1760.0°C.
SR01,TC,R,0,17600

Description • This command cannot be specified while

measurement/computation is in progress or

while a report is being created.

• Set parameters p3, p4, and p5 according to

the table in section 6.3.

• For parameters p4 and p5, enter a value using

5 digits or less excluding the decimal point.

The decimal position is fixed to the position

indicated in the table in section 6.3.

When computing the difference between channels

Syntax

SR p1,p2,p3,p4,p5,p6,p7<terminator>
p1: Channel number (01 to 20) (01 to 06 on the

CX1000)

p2: Range mode (DELTA)

p3: Input type

VOLT

DC voltage

TC

TC

RTD

RTD

DI ON/OFF input