External loop pid parameter settings, External loop control parameter settings – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 155

Advertising
background image

6-26

IM 04L31A01-17E

External Loop PID Parameter Settings
DT

Sets the external loop PID
parameter

Syntax

DT p1,p2,p3,p4<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)

p2: Loop number

1–4 for UT320/UT321/UT350/UT351

1–8 for UT420/UT450/UT520/UT550/UT750

p3: PID parameter name

SP: target setpoint (EU(0.0–100.0%)

A1-A4:

Alarm 1–4 setting value (or alarm

1–3 for the UT320/UT321/UT350/

UT351/UT420)

Measured value alarm/setting

value alarm: measured input

range of -100.0–100.0%

Deviation alarm: measured input

range span of -100.0–100.0%

Output value alarm: -5.0–105.0%

Time alarm (alarm 1 only): -1–

5999

P:

Proportional band setting (1–9999)

OH: Output limit upper limit value (-5.0–

105.0%)

OL: Output limit lower limit value (-5.0–

105.0%)

MR: Manual reset (-5.0–105.0%)

(Active when integral time I is OFF)

H:

On/off control hysteresis

During On/off control: Measured input

range span of -100.0–100.0%

During position proportional PID

control: 0.0-100.0%

DB: Dead band

During position proportional PID

control: 1.0-10.0%

DR: Correct back switching operation [2]

0: Back, 1: Right action [2]

PO: Preset output value (-5.0–105.0%)

For loops set to the CX’s external loop

tuning item, the external loop tuning

items take precedence.

p4: Parameter value

Measured value varies depending on p3’s

PID parameter.

Query

DT[ p1,p2 (,p3)]?

Example

Set external loop 1, group number 1, and PID

parameter SP to 1000.

DT1,1,SP,1000

Description • The parameter setting range differs depending

on the UT used.

• p4 is not needed for the UT320, UT321,

UT350, UT351, and UT420.

Integral time/derivative time settings

Syntax

DT p1,p2,p3,p4,p5<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)

p2: Loop number

1–4 for UT320/UT321/UT350/UT351

1–8 for UT420/UT450/UT520/UT550/UT750

p3: PID parameter name

I: Integral time

D: Derivative time

p4: Turns integration/differentiation On/Off

p5: Parameters when p4 is ON (1–6000)

Query

DT[ p1,p2 (,p3)]?

Example

Set external loop 2, group number 2, and PID

parameter D to 2000.

DT2,2,D,ON,2000

Description • Given the query, DT p1, p2?, returns the PID

parameter for p2's group number and the

setting values of each parameter.

• The PID parameters that can be set vary

depending on the control mode of the external

groups, and the control output type.

On/off control:

SP, A1-A4, H, DR, PO

Other than On/off control

SP, A1-A4, P, I, D, OH, OL, MR, DR, PO

Position proportional control

SP, A1-A4, H, P, I, D, OH, OL, MR, DR, DB,

PO

Internal switches primary

SP, A1-A4, P, I, D, OH, OL, MR, DR

External Loop Control Parameter Settings
DV

External loop control parameter
settings

Syntax

DV p1,p2,p3<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)

p2: Parameter names

MODE/AT/RL/SR/MOUT/SPN

p3: Parameter value

MODE: Switch between manual/automatic/

cascade

0: Automatic operation

1: Manual operation (cascade

control’s primary loop cannot be

selected)

2: Cascade operation (only

cascade control’s secondary

loop can be selected)

AT:

Execution and stop of auto tuning

0: Stop auto tuning

1: Execute PID number 1

:

8: Execute PID number 8

9: ALL

For UT320/UT321/UT350/ UT351,

5–8 is not needed.

6.5 Setting Commands (Measurement)