Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 311

Advertising
background image

App-52

IM 04L31A01-17E

Appendix 7 Messages

Code

Message

Character String and Details

SERVER

The server is not in a condition to provide the service.
Check that the server is in a condition in which service can be provided.

283

FTP command was not accepted.

Further details are provided by the character string that appears after error code 283.

Character String and Details

USER

Failed user name verification.
Check the user name setting.

PASS

Failed password verification
Check the password setting.

ACCT

Failed account verification.
Check the account setting.

TYPE

Failed to change the transfer type.
Check that the server supports the binary transfer mode.

CWD

Failed to change the directory.
Check the initial path setting.

PORT

Failed to set the transfer connection.
Check that the security function is disabled.

PASV

Failed to set the transfer connection.
Check that the server supports PASV commands.

SCAN

Failed to read the transfer connection settings.
Check that proper response to the PASV command is received from the server.

284

FTP transfer setting error.

Further details are provided by the character string that appears after error code 284.

Character String and Details

MODE

Internal processing error.

*1

LOCAL

Internal processing error.

*1

REMOTE

The destination file name is not correct.
Check that you have permission to create or overwrite files.

ABORT

File transfer abort was requested by the server.
Check the server for the reason for the abort request.

Advertising