App

Appendix

Parameters Related to Loop 1

41001

41002

41003

41004

41005

41006

41007

41008

41009

41010

41011

41012

41013
41014

41015

41016
41017
41018

41019

Parameter
per Loop

Enable/Disable the use of bias on
PV1, bias value, bias input type

Enable/Disable the use of bias on
PV2, bias value, bias input type

Enable/Disable the use of bias on
RemoteSP, bias value

Type of filter used on PV1,
enable/disable the use of the
filter, filter value

Type of filter used on PV2,
enable/disable the use of the
filter, filter value

Type of filter used on RemoteSP,
enable/disable the use of the
filter, filter value

Enable/Disable ratio setting and
the ratio value

Suppressing function On/Off

Ramp-rate-time unit

SP ramp-up-rate

SP ramp-down-rate

Switch between auto, manual,
and cascade control

Target setpoint number
Switch run/stop

Remote/local switching

Currently used PID number
OUT value in manual mode
Auto tuning (AT) status

Decimal point position of the
ratio value

–100% to 100% of the measurement span:
Bias value (bias enabled)

–30001 to –32768, 30001 to 32767:
Bias disabled
–100% to 100% of the measurement span:
Bias value (bias enabled)

–30001 to –32768, 30001 to 32767:
Bias disabled
–100% to 100% of the measurement span:
Bias value (bias enabled)

–30001 to –32768, 30001 to 32767:
Bias disabled
1 to 120: Filter value (filter enabled)

–30001 to –32768, 30001 to 32767:
Filter disabled
1 to 120: Filter value (filter enabled)

–30001 to –32768, 30001 to 32767:
Filter disabled
1 to 120: Filter value (filter enabled)

–30001 to –32768, 30001 to 32767:
Filter disabled
1 to 9999: Ratio value (ratio setting enabled)

–30001 to –32768, 30001 to 32767:
Ratio setting disabled
0: Suppressing function OFF
1: Suppressing function ON
0: Hour 2: Second
1: Minute
Value between 1 and the maximum
value of the measurement span excluding
the decimal point.

–30001 to –32768, 30001 to 32767:
OFF
Value between 1 and the maximum value of
the measurement span excluding the
decimal point.

–30001 to –32768, 30001 to 32767:
OFF
0: Auto switching
1: Manual switching
2: Cascade switching (valid only during

cascade control)

1 to 8: SP number
0: Stop
1: Start
0: Local
1: Remote
1 to 8: PID number
–50 to 1050: –5.0% to 105.0%
0: AT not in progress
1: AT in progress
0 to 4

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W
R/W

R/W

R
R/W
R

R

Modbus

Register

Number

Description

Register

Type

Value

Read/

Write

Appendix 6 Register Assignments