Program control parameters – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 299

Advertising
background image

App-40

IM 04L31A01-17E

Appendix 6 Register Assignments

• Program Control Parameters

D4001
D4002
D4003
D4004

D4005

D4006

D4007

D4008

D4009

D4010

D4011
D4012

D4013

D4014

D4015-D4020
D4021

D4022

D4023

D4024

D4025

D4026-D4030
D4031
D4032
D4033

Program run/stop
Hold program operation
Advance segment
Switch pattern number: Only
when program operation is
stopped
Pattern number in operation

Segment number in operation

Number of segments of the
pattern used currently
Remaining segment time of the
pattern in operation (hh)
Remaining segment time of the
pattern in operation (mm)
Remaining segment time of the
pattern in operation (ss)
Wait mode
Elapsed wait time in wait
mode (hh)
Elapsed wait time in wait
mode (mm)
Elapsed wait time in wait
mode (ss)
Reserved
Repeat setting of the current
pattern

Repeat frequency of the pattern
in operation
Remaining repeat frequency of
the pattern in operation
Repeat start number of the
pattern in operation
Repeat end number of the
pattern in operation
Reserved
Program control end signal
PV event status
Time event status

0: Stop, 1: Run
0: None, 1: in HOLD
1: Advance request
1: Pattern number 1
:
30: Pattern number 30
1: Pattern number 1
:
30: Pattern number 30
0-99
0 is the time between program control start
and program pattern control start.
1-99

0-99

*3

0-59

*3

0-59

*3

0: None, 1: in wait mode
0-99

*3

0-59

*3

0-59

*3

0
0: OFF
1: ON
2: Repeat infinite number of times
0-999

0-999

1-99

1-99

0
0: None, 1: Program control end

*4

*4

R/W
R/W
W
W

R

R

R

R

R

R

R
R

R

R

R
R

R

R

R

R

R
R
R
R

Modbus

Register

Number

Description

Register Type

Value

Read/

Write

*3 To read the remaining segment time and the elapsed wait time (hh:mm:ss), read three registers.
*4 Each register bit (16 bits) indicates the event status corresponding to each event number. When

the setting is “1,” the event is ON. When the data is read using ladder communications, the 16-
bit signed data converted to BCD is returned. Therefore, the host computer must convert the
value to 16-bit signed integer.