Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 153

Advertising
background image

6-24

IM 04L31A01-17E

p4: Internal switch number (SW001-SW036, or

SW001-SW018 for the CX1000)

p5: ON DO number (DI001-DI006, DI101-

DI106, DI201-DI206, RI001-RI012, or

DI001-DI006 for the CX1000)

p6: OFF DO number (DI001-DI006, DI101-

DI106, DI201-DI206, RI001-RI012, or

DI001-DI006 for the CX1000)

Query

DX p1?

Example

Set DIO operation monitoring number 2 so that

the ON status of internal switch SW003 is output

from DO002, and the OFF status is output from

DO003, and monitored.

DX2,ON,DO-2,SW003,DO002,DO003

When set to DIO-11

Syntax

DX p1,p2,p3,p4,p5,p6<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON(Off/On)

p3: Type (DI-1, DO-1, DO-2, DIO-11, DIO-12,

DO-2P, DIO-12P)

Set to DIO-11 here.

p4: Internal switch number (SW001-SW036, or

SW001-SW018 for the CX1000)

p5: DO number (DI001-DI006, DI101-DI106,

DI201-DI206, RI001-RI012, or DI001-DI006

for the CX1000)

p6: DI number (DI001-DI006, DI101-DI106,

DI201-DI206, RI001-RI012, or DI001-DI006

for the CX1000)

Query

DX p1?

Example

Set DIO operation monitoring number 2 to so

that the status of internal switch SW003 is output

from DO002, and DIO03’s status is monitored.

DX2,ON,DIO-11,SW003,DO002,DI003

When set to DIO-12 or DIO-12P

Syntax

DX p1,p2,p3,p4,p5,p6,p7<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON(Off/On)

p3: Type (DI-1,DO-1, DO-2, DIO-11, DIO-12,

DO-2P, DIO-12P)

Set to DIO-12 or DIO-2P here.

p4: Internal switch number (SW001-SW036, or

SW001-SW018 for the CX1000)

p5: ON DO number (DI001-DI006, DI101-

DI106, DI201-DI206, RI001-RI012, or

DI001-DI006 for the CX1000)

p6: OFF DO number (DI001-DI006, DI101-

DI106, DI201-DI206, RI001-RI012, or

DI001-DI006 for the CX1000)

p7: DI number (DI001-DI006, DI101-DI106,

DI201-DI206, RI001-RI012, or DI001-DI006

for the CX1000)

Query

DX p1?

Example

Set DIO operation monitoring number 2 so that

the ON status of internal switch SW003 is output

from DO002, the OFF status is output from

DO003, and DIO02's status is monitored.

DX2,ON,DIO-12,SW003,DO002,DO003,

DI002

Description With DO-2, DO-2P, DIO-12, and DIO-12P, ON

DO and OFF DO cannot be set to the same DO.

DY

Sets the DIO operation
monitoring function tag and tag
comment

Syntax

DX p1,p2,p3<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: Tag (8 alphanumeric characters, no

symbols)

p3: Tag comment (8 alphanumeric characters,

no symbols)

Query

DX[ p1]?

Example

Set DIO operation monitoring function number

3’s tag to test, and the tag comment to onoff.

DX3,test,onoff

DZ

Sets the DIO operation
monitoring function label and
display color

Syntax

DZ p1,p2,p3,p4,p5<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON label (8 alphanumeric characters, no

symbols)

p3: ON display color

Red, Green, B.violet, Brown, Orange,

Y.green, Lightblue, Violet, Lime, Cyan,

Darkblue, Purple

p4: OFF label (8 alphanumeric characters, no

symbols)

p5: OFF display color

Red, Green, B.violet, Brown, Orange,

Y.green, Lightblue, Violet, Lime, Cyan,

Darkblue, Purple

Query

DZ[ p1]?

Example

Set DIO operation monitoring function number

3’s ON label to start, the ON display color to red,

the OFF label to stop, and the OFF display color

to green.

DZ3,start,Red,stop,Green