Chapter 4 modbus protocol, 1 modbus protocol specifications, Modbus protocol specifications -1 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 95

Advertising
background image

4-1

IM 04L31A01-17E

4

Modbus Protocol

4.1

Modbus Protocol Specifications

The Modbus protocol can be used over the serial interface (RS-232 or RS-422/485).

The Modbus specifications of the CX are as follows.

Specifications

Description

Transmission media

RS-232 or RS-422/485

Control

RS-232: None only

(Flow control is not available.)

RS-422/485: None only

Baud rate

1200, 2400, 4800, 9600, 19200, and 38400

Start bit

Fixed to 1 bit

Stop bit

Fixed to 1 bit

Parity

Select Odd, Even, or None (no parity).

Transmission mode

RTU (Remote Terminal Unit) mode only
• Data length

8 bits

• Data interval

24 bits or less*

• Error detection

Uses CRC-16

* Determines message termination with a time interval equal to

3.5 characters or more.

Slave address

RS-232: 1 to 32
RS-422/485: 1 to 32

The function codes of Modbus protocol that are supported by the CX are as follows
Master Function

Function Code

Function

Operation

3

Reads the hold register

The CX reads the data in the hold

(4xxxx and 4xxxxx)

register of another device.

4

Reads the hold register

The CX reads the data in the input

(3xxxx and 3xxxxx)

register of another device.

Slave Function

Function Code

Function

Operation

3

Reads the hold register

The master device can read the

(4xxxx)

communication input data written using
function codes 6 and 16.

4

Reads the input register

The master device reads the computed,

(3xxxx)

measured, control, and time data of the CX.

6

Single-write to the hold register The master device writes to the register of
(4xxxx)

the CX.

8

Loopback test

The master device performs a loopback test
of the CX. The CX only supports message
return (test code 0x00*).

16

Writes to the hold register

The master device writes to the

(4xxxx)

communication input data of the CX.

*

Hexadecimal “00”.

Chapter 4 Modbus Protocol