Appendix 6 Register Assignments

• Control Channel Bias and Filter Values When PV/SP Computation is ON

When PV/SP computation is ON, the bias and filter values for PV1 and PV2 specified by
loops is set by control channel.

D4901

D4902

:
D4910

D4911

D4912

:
D4920

Enable/Disable the use of bias on
CI01, bias value
Enable/Disable the use of bias on
CI02, bias value, bias input type
:
Enable/Disable the use of bias on
CI10, bias value
Type of filter used on CI01,
enable/disable the use of the
filter, filter value
Type of filter used on CI02,
enable/disable the use of the
filter, filter value
:
Type of filter used onCI10,
enable/disable the use of the
filter, filter value

–100% to 100% of the control input range:
Bias value (bias enabled)
–30001 to –32768, 30001 to 32767:
Bias disabled

1 to 120: Filter value (filter enabled)
–30001 to –32768, 30001 to 32767:
Filter disabled

R/W

R/W

Modbus

Register

Number

Description

Register

Type

Value

Read/

Write