9-9

IM 04L31A01-17E

9

Green Series Communications

• Control output type

If the connecting model is UT series, select from the following:

Control Output Type

Soft Key Menu

Time proportional PID relay contact output

Relay

Time proportional PID voltage pulse output

Voltage-pulse

Current output

Current-output

On/Off-control relay contact output

On/Off-control

If the connecting model is “ETC,” you cannot select the control output type.

• Alarm type

If the connecting model is UT series, select from the following. However, the
selectable items vary depending on the connecting model. See the UT Series
user’s manual.

Alarm Type

Soft Key Menu*

Off

Off

PV high-limit alarm (energize)

PV-H-E

PV low-limit alarm (energize)

PV-L-E

Deviation high-limit alarm (energize)

Dev-H-E

Deviation low-limit alarm (energize)

Dev-L-E

Deviation high-limit alarm (deenergize)

Dev-H-D

Deviation low-limit alarm (deenergize)

Dev-L-D

Deviation high & low limit alarm (energize)

Dev-HL-E

Deviation within high & low limits alarm (energize)

D-W-HL-E

PV high-limit alarm (deenergize)

PV-H-D

PV low-limit alarm (deenergize)

PV-L-D

PV high-limit alarm (energize/hold)

PV-H-ES

PV low-limit alarm (energize/hold)

PV-L-ES

Deviation high-limit alarm (energize/hold)

Dev-H-ES

Deviation low-limit alarm (energize/hold)

Dev-L-ES

Deviation high-limit alarm (deenergize/hold)

Dev-H-DS

Deviation low-limit alarm (deenergize/hold)

Dev-L-DS

Deviation high & low limit alarm (energize/hold)

Dev-HL-ES

Deviation within high & low limits alarm (energize/hold)

D-W-HL-ES

PV high-limit alarm (deenergize/hold)

PV-H-DS

PV low-limit alarm (deenergize/hold)

PV-L-DS

Timer, upward detection, hours & minutes

TimeUp1

Timer, downward detection, hours & minutes

TimeDown1

Timer, upward detection, minutes & seconds

TimeUp2

Timer, downward detection, minutes & seconds

TimeDown2

Sensor grounding alarm

Sensor

Self diagnosis output

Prog-Diag

FAIL output

FAIL

SP high-limit

SP-H

SP low-limit

SP-L

Output high-limit

Out-H

Output low-limit

Out-L

Heater burnout alarm 1

Burnout1

Heater burnout alarm 2

Burnout2

* Some of the dislayed characters are abbreviated even further on the CX1000.

If the connecting model is UT320, UT321, UT350, UT351, or UT420, you
cannot set alarm number 4.

If the connecting model is UT420, UT450, UT520, UT550, or UT750, you can
set the timer function alarm type only for alarm number 1.

The heater burnout alarms can be used if the connecting model is UT320,
UT321, UT350, or UT351.

If the connecting model is “ETC,” you cannot select the alarm type.