6.5 Setting Commands (Measurement)

• This command cannot be specified while

measurement/computation is in progress or

while a report is being created.

SI

Sets the rolling average of the
computation channel

When turning OFF the rolling average of the
computation channel

Syntax

SI p1,p2<terminator>
p1: Computation channel number (31 to 60) (31

to 42 on the CX1000)

p2: Rolling average ON/OFF (OFF)

Query

SI[ p1]?

Example

Turn OFF the rolling average of computation

channel number 31.

SI31,OFF

Description This command can be used on models with the

computation function option /M1.

When turning ON the rolling average of the
computation channel

Syntax

SI p1,p2,p3,p4<terminator>
p1: Computation channel number (31 to 60) (31

to 42 on the CX1000)

p2: Rolling average ON/OFF (ON)

p3: Sampling interval (1S, 2S, 3S, 4S, 5S, 6S,

10S, 12S, 15S, 20S, 30S, 1MIN, 2MIN,

3MIN, 4MIN, 5MIN, 6MIN, 10MIN, 12MIN,

15MIN, 20MIN, 30MIN, 1H)

p4: Number of samples (1 to 64)

Query

SI[ p1]?

Example

Turn the rolling average of computation channel

31 ON, set the sampling interval to 1 minute, and

the number of samples to 20.

SI31,ON,1MIN,20

Description This command can be used on models with the

computation function option /M1.

SJ

Sets the TLOG timer

Syntax

SJ p1,p2,p3<terminator>
p1: Computation channel number (31 to 60) (31

to 42 on the CX1000)

p2: Timer (1 to 3)

p3: Conversion of the time unit for TLOG.SUM

computation

OFF No conversion

/S

Convert as though the physical

values are integrated in units of

seconds.

/MIN Convert as though the physical

values are integrated in units of

minutes.

/H

Convert as though the physical

values are integrated in units of

hours.

Query

SJ[ p1]?

Example

Set timer 1 to computation channel number 31.

No conversion of time unit.

SJ31,1,OFF

Description • This command can be used on models with

the computation function option /M1.

• This command cannot be specified while

computation is in progress.

• About p3

Because the sampled data are integrated over

each scan interval, the physical value

integrated over a given period may be

different from the actual integrated value.

This occurs if the given period is not equal to

the scan interval. In these cases, set p3 to

the unit of the integration time desired. The

integrated value is found according to the

following conversion equations that depend

on the parameter.

OFF

Σ(Measured value)

/S

Σ(Measured value) × scan interval

/MIN

Σ(Measured value) × scan interval/60

/HOUR Σ(Measured value) × scan interval/

3600

The unit of the scan interval is seconds.

SS

Sets the date and time at which
to switch the daylight savings
time

When the switching the daylight savings time is
OFF

Syntax

SS p1,p2<terminator>
p1

Summer time or winter time (SUMMER,

WINTER)

p2

Enable/disable (ON/OFF) the switching

(OFF)

Query

SS[ p1]?

Example

Set the summer time is OFF.

SSSUMMER,OFF

Description This command can be used on models with the

display language code “-2.”

When the switching the daylight savings time is
ON

Syntax

SS p1,p2,p3<terminator>
p1

Summer time or winter time (SUMMER,

WINTER)

p2

Enable/disable (ON/OFF) the switching

(ON)

p3

Date and time (yy/mm/dd hh fixed form.

Insert a space between dd and hh.)

yy

Year (00 to 99)

mm

Month (01 to 12)

dd

Day (01 to 31)

hh

Hour (00 to 23)

Query

SS[ p1]?