External loop setting (parameter address setting) – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 182

Advertising
background image

6-53

IM 04L31A01-17E

6

Command

GH

External loop parameter 1,
control span lower/upper limit

Syntax

GH p1,p2,p3<terminator>
p1: Loop number (Ext1 to Ext16) (Ext1 to Ext4

on the CX1000)

p2: Control span lower

p3: Control span upper

Query

GH[ p1]?

Example

Set the control span lower limit of external loop

10 to 0, the upper limit to 20000.

GHEXT10,0,20000

GQ

External loop parameter 3,
control mode/control output type

Syntax

GQ p1,p2,p3<terminator>
p1: Loop number (Ext1 to Ext16) (Ext1 to Ext4

on the CX1000)

p2: Control mode*

1

p3: Control output type*

2

*1:

SingleLoopControl/

CascadePrimaryLoop/

CascadeSecondaryLoop/

CascadeControl/ControlBackUp/

PVSwitching/

PVAutoSelector/PVHoldFunction/

DualLoopControl/Temperature-

Humidity/

Cascade-2Uni/PVSwitching-2Uni/

PVAutoSelector-2Uni

*2:

Relay,Voltage-pulse,Current-output,

On/Off-control

Query

GQ[ p1]?

Example

Set the control mode of external loop 14 to 2

universal input PV auto selector and the control

output type to On/Off-control relay contact

output.

GQEXT14,PVAutoSelector-2Uni,

ON/OFF-CONTROL

GN

External loop parameter 2, alarm
number/alarm type

Syntax

GN p1,p2,p3<terminator>
p1: Loop number (Ext1 to Ext16) (Ext1 to Ext4

on the CX1000)

p2: Alarm number (1 to 4) (numbers 1 to 3 are

valid for UT320/UT350/UT420)

p3: Alarm type*

1

*1:

PV-High(Energ),PV-Low(Energ),

Deviation-High(Energ),

Deviation-Low(Energ),

Deviation-High(Deenerg),

Deviation-Low(Deenerg),

Deviation-H&L(Energ),

Dev-within-H&L(Energ),

PV-High(Deenerg),PV-Low(Deenerg),

PV-High(Energ/Standby),

PV-Low(Energ/Standby),

Dev-High(Energ/Standby),

Dev-Low(Energ/Standby),

Dev-High(Deenerg/Standby),

Dev-Low(Deenerg/Standby),

Dev-H&L(Energ/Standby),

Dev-w-H&L(Energ/Standby),

PV-High(Deenerg/Standby),

PV-Low(Deenerg/Standby),

Timer-upward(h:m),Timer-

downward(h:m),

Timer-upward(m:s),Timer-

downward(m:s),

Sensor-grounding,Problem-

diagnostic,

FAIL-output,SP-High,SP-Low,

Output-High,Output-Low

Heater-burnout1,Heater-burnout2

Query

GN[ p1,p2]?

Example

Set external loop 11 alarm number 1 to PV high-

limit alarm (deenergize/standby).

GNEXT11,1,PV-HIGH(DEENERG/STANDBY)

External Loop Setting (Parameter
Address Setting)
GW

Sets the external loop parameter
address

Syntax

GW p1,p2,p3<terminator>
p1: Loop number (Ext1 to Ext16) (Ext1 to Ext4

on the CX1000)

p2: Parameter type (PV, SP, OUT, Mode, R/L,

S/R, Alarm, SP.No, PID.No,AT)

(If the connecting model is “Other,”

parameters up to OUT are valid.)

p3: Register address (30001 to 39999, 40001 to

49999, 300001 to 365535, 400001 to 465535)

Query

GW[ p1,p2]?

Example

Set the register address of parameter PV of

external loop 3 to 40003.

GWEXT3,PV,40003

6.8 Basic Setting Commands (Control)