IM 04L31A01-17E

6

Command

Detail Settings (Control Function
Settings)
HF

Sets the setpoint

Syntax

HF p1,p2,p3,p4,p5<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Enable/disable SP tracking (Off, On).

p3: Enable/disable PV tracking (Off, On).

p4: SP high-limit EU (0.0 to 100.0%)

High-limit > Low-limit

p5: SP low-limit EU (0.0 to 100.0%)

High-limit > Low-limit

Query

HF[ p1]?

GL

Sets the output velocity limiter

Syntax

GL p1,p2,p3<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Enable/disable output velocity limiter (Off,

On)

p3: Output velocity limiter value (0.1 to 100.0%/s)

Query

GL[ p1]?

Description This command cannot be used when the control

output type (set using the GQ command) is set to

“On/Off-control.”

GA

Sets the anti-reset windup
function

Syntax

GA p1,p2,p3<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Anti-reset windup function (Auto, Manual)

p3: Deviation width (50.0 to 200.0)

Can be specified only when p2 is set to

Manual.

Query

GA[ p1]?

Description This command cannot be used when the control

output type (set using the GQ command) is set to

“On/Off-control.”

Detail Settings (Hysteresis (Alarm, PV
Event))
AP

Sets the alarm hysteresis

Syntax

AP p1,p2,p3<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Alarm number (1 to 4)

p3: Hysteresis EUS (The hystersis range is the

range of values that results from multiplying the

measurement span by 0.0 to 10.0%. However,

when the alarm type is output high-limit or output

low-limit, the range is 0.0 to 10.0% as-is.)

Query

AP[ p1,p2]?

PH

Sets the PV event hysteresis

Syntax

PH p1,p2<terminator>
p1: PV event number (1 to 16)

p2: Hysteresis (0.0 to 10.0%)

Query

PH[ p1]?

Detailed Settings (DIO Operation
Monitoring Function Settings)
DX

DIO operation monitoring
function settings

When DIO operation monitoring function is OFF

Syntax

DX p1,p2<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: Off(Off/On)

Query

DX p1?

Example

When DIO operation monitoring number 2 is

OFF

DX2,OFF

When set to DI-1

Syntax

DX p1,p2,p3,p4<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON(Off/On)

p3: Type (DI-1, DO-1, DO-2, DIO-11, DIO-12,

DO-2P, DIO-12P)

Set to DI-1 here.

p4: DI number (DI001-DI006, DI101-DI106,

DI201-DI206, RI001-RI012, or DI001-DI006

for the CX1000)

Query

DX p1?

Example

Set DIO operation monitoring number 2 so that it

monitors DI002 input.

DX2,ON,DI-1,DI002

When set to DO-1

Syntax

DX p1,p2,p3,p4,p5<terminator>

p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON(Off/On)

p3: Type (DI-1, DO-1, DO-2, DIO-11, DIO-12,

DO-2P, DIO-12P)

Set to DO-1 here.

p4: Internal switch number (SW001-SW036, or

SW001-SW018 for the CX1000)

p5: DO number (DI001-DI006, DI101-DI106,

DI201-DI206, RI001-RI012, or DI001-DI006

for the CX1000)

Query

DX p1?

Example

Set DIO operation monitoring number 2 so that

the status of internal switch SW003 is output

from DO002, and monitored.

DX2,ON,DO-1,SW003,DO002

When set to DO-2 or DO-2P

Syntax

DX p1,p2,p3,p4,p5,p6<terminator>
p1: DIO operation monitoring function number

(01–36, 01–12 for the CX1000)

p2: ON(Off/On)

p3: Type (DI-1, DO-1, DO-2, DIO-11, DIO-12,

DO-2P, DIO-12P)

Set to DO-2 or DO-2P here.

6.4 Setting Commands (Control)