6-54

IM 04L31A01-17E

6.9

Control Commands

Control Commands
CA

Switches between auto, manual,
and cascade control

Syntax

CA p1,p2<terminator>
p1: Switch between auto, manual, and cascade

operation (0, 1, 2)

0: Automatic switching

1: Manual switching

2: Cascade switching

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

Example

Set the operation mode of loop 4 to cascade.

CA2,4

OC

Switches run/stop

Syntax

OC p1,p2<terminator>
p1: Switch run/stop (0, 1)

0: Stop

1: Run

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

Example

Switch loop 5 to run.

OC1,5

RL

Switches remote/local

Syntax

RL p1,p2<terminator>
p1: Switch remote/local (0, 1)

0: Local

1: Remote

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

Example

Set the input of loop 1 to remote.

RL1,1

OS

Stops/Starts control operation
(common to all loops)

Syntax

OS p1<terminator>
p1: Stop control operation

0: Stop

1: Start

Example

Start control operation.

OS1

SN

Switches target setpoint number

Syntax

SN p1,p2<terminator>
p1: Target setpoint number SP (1 to 8)

1 to 8: Target setpoint number 1 to target

setpoint number 8

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

Example

Set the target setpoint number of loop 5 to 8.

SN8,5

PX

Resets/Runs program

Syntax

PX p1<terminator>
p1: Switch reset/run (0, 1)

0: RESET

1: RUN

Example

Start program operation

PX1

HU

Holds program operation

Syntax

HU p1<terminator>
p1: Hold program operation (0, 1)

0: Release hold

1: Hold

Example

Hold the program operation.

HU1

AD

Advances program operation

Syntax

AD p1<terminator>
p1: Segment advance request during program

operation (1)

1: Segment advance request

Example

AD1

PN

Switches the pattern number

Syntax

PN p1<terminator>
p1: Program pattern number (1 to 30)

1 to 30: Pattern number 1 to pattern

number 30

Example

Set the program pattern number to 10.

PN10

HJ

Changes the manual output
setting

Syntax

HJ p1,p2<terminator>
p1: Manual output setting (–50 to 1050 (–5.0 to

105.0%)). However, within the output high-

limit and low-limit.

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

Example

Set the manual output setting of loop 1 to 25.0%.

HJ250,1

HV

Requests auto tuning

Syntax

HV p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: 0 OFF

1 Carry out PID number 1

2 Carry out PID number 2

3 Carry out PID number 3

4 Carry out PID number 4

5 Carry out PID number 5

6 Carry out PID number 6

7 Carry out PID number 7

8 Carry out PID number 8

9 all

Example

Execute PID number 1 of loop 1.

HV1,1

6.8 Basic Setting Commands (Control)