3-1

IM 04L31A01-17E

Serial Interface

3

3.1

Serial Interface Specifications

The specifications of the two types of serial interfaces (options), RS-232 and RS-422/
485, of the CX are given below.

RS-232 Specifications

Connector type

D-Sub 9-pin plug

Electrical and mechanical specifications

Conforms to EIA-574 (9-pin EIA-232 (RS-232))

Connection

Point-to-point

Transmission mode

Half-duplex

Synchronization

Start-stop synchronization

Baud rate

Select from 1200, 2400, 4800, 9600, 19200, and 38400
[bps].

Start bit

Fixed to 1 bit

Data length

Select 7 or 8 bits

To output data in BINARY format, make sure to set the data length to 8 bits.)

Parity

Select Odd, Even, or None (no parity).

Stop bit

Fixed to 1 bit

Hardware handshaking

Select whether to set the RS and CS signals to TRUE
always or use them as control lines.

Software handshaking

Select whether to use the X-ON and X-OFF signals to
control the transmission data or both transmission and
reception data.
X-ON (ASCII 11H) and X-OFF (ASCII 13H)

Received buffer length

2047 bytes

RS-422/485 Specifications

Terminal block type

Number of terminals: 6, terminal attachment screws:
ISO M4/nominal length of 6 mm

Electrical and mechanical specifications

Conforms to EIA-422 (RS-422) and EIA-485 (RS-485)

Connection

Multidrop

For a four-wire system

1:32

For a two-wire system

1:31

Transmission mode

Half-duplex

Synchronization

Start-stop synchronization

Baud rate

Select from 1200, 2400, 4800, 9600, 19200, and 38400
[bps].

Start bit

Fixed to 1 bit

Data length

Select 7 or 8 bits

Parity

Select Odd, Even, or None (no parity).

Stop bit

Fixed to 1 bit

Received buffer length

2047 bytes

Escape sequence

Open and close

Electrical characteristics

6 points consisting of FG, SG, SDB, SDA, RDB, and RDA
The SG, SDB, SDA, RDB, and RDA terminals and the
internal circuitry of the CX are functionally isolated.
The FG terminal is the frame ground.

Communication distance

Up to 1.2 km

Terminator

External: Recommended resistance is 120 Ω , 1/2 W

Chapter 3 Serial Interface

Advertising