Setting (Correcting) the Detail Information

• If the data is not set correctly using auto setting, you can set (correct) the items

using the operation keys.

• Select the turning parameters from the following:

Tuning parameter

Soft Key Menu (Item ID)

Target setpoint

SP

Alarm value 1

A1

Alarm value 2

A2

Alarm value 3

A3

Alarm value 4

A4

Proportional band

P

Integral time

I

Derivative time

D

Output high-limit

OH

Output low-limit

OL

Manual reset

MR

Relay hysteresis

H

Control direction

DR

Dead band

DB

Preset output

PO

Others

ETC

• If you select an item ID (tuning parameter) from “SP, A1, A2, A3, A4, P, I, D, OH,

OL, MR, H, DR, DB, and PO,” the preset setup information is assigned to the detail
information items (item name, register address, decimal point position, high and
low limits of the value range).

• If the connecting model is UT320, UT321, UT350, UT351, or UT420, you cannot

set the tuning parameter of alarm value 4 (A4).

• When the connecting model is “ETC,” you can only set “ETC” for the tuning

parameter.

• Item ID

Item IDs are used to display the tuning parameters on the setting display of the CX.
A list of tuning parameters and item ID is indicated above.

• Item name

You can set the name of the tuning parameter using up to 6 alphanumeric
characters.

• Registers address

You can set the register address in the following range.
30001 to 39999, 40001 to 49999, 300001 to 365535, 400001 to 465535

• Decimal point

Set the decimal point position in the range of 0 to 4.

No decimal point when set to 0.

One digit to the right of the decimal when set to 1.

Two digits to the right of the decimal when set to 2.

Three digits to the right of the decimal when set to 3.

Four digits to the right of the decimal when set to 4.

• Range lower and upper

Set the limits in the range of –30000 to 30000.

The decimal point position above is used. For example, if the decimal point
position is set to “1” and you enter “10000,” it is taken to be “1000.0”.

9.6 External Loop Setting > Tuning Setting