Li saves the setup data, Cm sets the communication input data, Em starts/stops e-mail transmission function – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 168: Dp do/internal switch status settings

Advertising
background image

6-39

IM 04L31A01-17E

6

Command

LI

Saves the setup data

Syntax

LI p1<terminator>
p1: File name (up to 8 characters)

Example

Save the setup data of both setting and basic

setting commands to the file SETFILE2.

LISETFILE2

Description • A “.pcl” extension is attached to the saved file.

• This command cannot be specified on models

that do not have an external storage device or

when a medium is not inserted into the drive.

• This command cannot be used while the

setup data file is being output (specified using

the FE command).

• This command cannot be used when the #1

Program parameter setting display under #7

Program-control parameters in Set mode is

shown(or after sending the PB command).

CM

Sets the communication input
data

Syntax

CM p1,p2<terminator>
p1: Communication input data number (C01 to

C30)

p2: Communication input data

The selectable range is –9.9999E+29 to –

1.0000E–30, 0, and 1.0000E–30 to

9.9999E+29

(The + sign of “E+” can be omitted.)

Query

CM?

Example

Set 1.0000E–10 to communication input data

number C01.

CMC01,1.0000E-10

Description This command can be used on models with the

computation function option /M1.

EM

Starts/stops e-mail transmission
function

Syntax

EM p1<terminator>
p1: Operation type

0 Start

1 Stop

Example

Start the e-mail transmission function.

EM0

Description To use the e-mail transmission function, you

must set the Ethernet interface, e-mail address,

and contents to be transmitted. For details on

setting these items, see section 2.11.

DL

Mode switching for the DIO
operation monitoring function

Syntax

DL p1,p2<terminator>
p1: DIO operation monitoring number (01–36,

1–12 for the CX1000)

p2: Auto/manual switching

0 Automatic

1 Manual

Example

When the output mode for DIO operation

monitoring number 4 is Automatic.

DL4,0

DM

Sets the manual output value for
DIO operation monitoring
function

Syntax

DM p1,p2<terminator>
p1: DIO operation monitoring number (01–36,

1–12 for the CX1000)

p2: Manual output value

0 Off

1 On

Example

Set DIO operation monitoring number 4 to

Manual.

DM4,1

DP

DO/internal switch status
settings

Syntax

DP p1,p2<terminator>
p1: Relay numbers

DO001-DO006

DO101-DO106

DO201-DO206

RO001–RO012 (expansion module)

SW001–SW036 (internal switch)

DO001-DO006 and SW001-SW018 for the

CX1000.

p2: Status of relay (switch)

0 Off

1 On

Example

Turn internal switches SW008 ON.

DPSW008,1

6.6 Setting Commands (Operation)