5-1
IM 04L31A01-17E
5
Ladder Communication Protocol
5.1
Ladder Communication Protocol
Specifications
The ladder communication protocol can be used over the serial interface (RS-232 or RS-
422/485).
The ladder communication specifications of the CX are as follows.
Specifications
Description
Transmission media
RS-232 or RS-422/485
Control
RS-232: None only
(Flow control is not available)
RS-422/485: None only
Baud rate
1200, 2400, 4800, 9600, 19200, and 38400
Start bit
Fixed to 1 bit
Stop bit
Fixed to 1 bit
Parity
Select Odd, Even, or None (no parity).
Communication address
1 to 32