Command

GS

Sets remote input

Syntax

GS p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Remote input

(Off, Remote)

Query

GS[ p1]?

Example

Use the remote of loop 2.

GS2,REMOTE

HG

Sets the alarm mode

Syntax

HG p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Alarm mode

(Always,Stop,Stop/Man)

Query

HG[ p1]?

Example

Set the alarm mode of loop 2 to stop.

HG2,STOP

HY

Sets the SP number selection
source

Syntax

HY p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: SP number selection source (Off, On)

Example

Turn On loop 1.

HY1,ON

MY

Turns Off/On the PV/SP
computation

Syntax

MY p1<terminator>
p1: PV/SP computation function Off/On

Query

MY?

MZ

Sets the CLOG error

Syntax

MZ p1<terminator>
p1: CLOG error processing (skip, error)

Query

MZ?

Output Processing
GF

Sets the output processing

Syntax

GF p1,p2,p3,p4<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Control output type*

p3: Cycle time (1 to 1000)

p4: Analog output-type

(4-20 mA, 0-20 mA, 20-4 mA, 20-0 mA)

*: Relay

Voltage-pulse

Current-output

On/Off-control

Query

GF[ p1]?

Example

Set the control output type of loop 4 to current

output, cycle time to 600 s, and analog output

type to 4-20 mA.

GF4,CURRENT-OUTPUT,600,4-20MA

Relay
GR

Sets relay parameters

Syntax

GR p1,p2<terminator>
p1: Enable/Disable the FAIL function (Off, On)

p2: Enable/disable self diagnosis function (Off,

On)

Query

GR?

Example

Turn Off the FAIL function and turn On the self

diagnosis function

GROFF,ON

GE

Sets relay action

Syntax

GE p1,p2,p3<terminator>
p1: Module type

*1

p2: Relay number

*2

p3: Relay action

*3

*1:

CTRL1-2, CTRL3-4, CTRL5-6

EXTDIO (CTRL1-2 only on the

CX1000)

*2:

DI001 to DI006

DI101 to DI106

DI201 to DI206

RI001 to RI012 (expansion module)

On the CX1000: DI001 to DI006

*3:

De_energize/Hold, De_energize/

Nonhold,

Energize/Hold, Energize/Nonhold

Query

GE[ p1,p2]?

Example

The relay number 10 of the expansion module to

“Energize/Hold”.

GEEXTDIO,RO010,ENERGIZE/HOLD