Su sets the user key, Sk sets the computation constant – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 162

Advertising
background image

6-33

IM 04L31A01-17E

6

Command

6.5 Setting Commands (Measurement)

SY

Sets the 4 screen display
(CX2000 only)

Syntax

SY p1,p2,p3,p4,p5,p6,p7,p8,p9,p10
<terminator>

p1: 4 screen display number (1 to 4)

p2: Four screen display name (up to 16

characters)

p3: The display item of the upper left quadrant

of the divided screen

TREND

Trend display

DIGITAL

Digital display

BAR

Bar graph display

OVERVIEW

Overview display

(Alarm indicator)

ALARM

Alarm summary display

MESSAGE

Message summary

display

MEMORY

Memory summary

display

FACEPLATE

Control faceplate

CONTROLLER

Control digital display

HYBRID

Control bar graph

display

CTRLOVER

Control overview

CTRLDO

DO status display

CTRLSUMMARY

Control operation

summary

CTRLSW

Internal switch status

display

EVENTSUMMARY Program event

summary

p4: Group number to be displayed at quadrant 1

The selectable range of group numbers

varies depending on the display type as

follows:

TREND/DIGITAL/BAR: 1 to 10

OVERVIEW/ALARM/MESSAGE/MEMORY:

Group specification is invalid.

FACEPLATE/CONTROLLER/HYBRID: 1 to

8

CTRLOVER/CTRLDO/CTRLSUMMARY/

EVENTSUMMARY: Group specification is

invalid.

p5: Display item on the lower left screen (screen

2) of the 4 screens (same selections as p3)

p6: Number of the group to be displayed on the

lower left screen (screen 2)

p7: Display item on the upper right screen

(screen 3) (same selections as p3)

p8: Number of the group to be displayed on the

upper right screen (screen 3)

p9: Display item on the lower right screen

(screen 4) (same selections as p3)

p10: Number of the group to be displayed on the

lower right screen (screen 4)

Query

SY[ p1]?

Example

Set the four screen display number to 1, four

screen display name to 4DISPLAY1, the display

item of screen 1 to trend display, the group

number to display in screen 1 to 1, the display

item of screen 2 to digital display, the group

number to display in screen 2 to 2, the display

item of screen 3 to bar graph display, the group

number to display in screen 3 to 3, the display

item of screen 4 to message summary display,

and the group number to display in screen 4 to 4.

SY1,4DISPLAY1,TREND,1,DIGITAL,2,

BAR,3,MESSAGE,4

Description The p4, p6, p8, and p10 parameters are valid

when p3, p5, p7, and p9 are set to a display

other than OVERVIEW, respectively.

SU

Sets the USER key

Syntax

SU p1<terminator>
p1: Key action

NONE

No action

ALARM ACK

Alarm acknowledge

MANUAL SAMPLE Manual sample

TRIGGER

External trigger input

(Event data)

MESSAGE1

Write message 1

MESSAGE2

Write message 2

MESSAGE3

Write message 3

MESSAGE4

Write message 4

MESSAGE5

Write message 5

MESSAGE6

Write message 6

MESSAGE7

Write message 7

MESSAGE8

Write message 8

SNAPSHOT

Snapshot

MATH START/STOP

Start/Stop MATH

MATH RESET

Reset MATH

Query

SU?

Example

Set the key action to the snapshot.

SUSNAPSHOT

SK

Sets the computation constant

Syntax

SK p1,p2<terminator>
p1: Computation constant number (K01 to K30)

(K01 to K12 on the CX1000)

p2: Constant (up to 11 characters)

The selectable range is –9.9999E+29 to –

1.0000E–30, 0, and 1.0000E–30 to

9.9999E+29

(The + sign of “E+” can be omitted.)

Query

SK[ p1]?

Example

Set constant 1.0000E–10 for computation

constant number K01.

SKK01,1.0000E-10

Description • This command can be used on models with

the computation function option /M1.