Connection Example with the Other Instruments

You can connect the CX as a host to multiple Green series controllers or connect the CX
to a host computer such as a PC.
• If the host uses an RS-232 interface, use a converter. For recommended converters,

see the latter section “Serial Interface Converter.”

• The two-wire cable can be used only when using the Modbus protocol. For the

configuration procedure, see section 3.5.

Four-Wire System

In general, the instrument and the host computer are connected with the transmission
and reception lines crossed. Terminal instruments are connected to each other using
straight connections.

Terminator (externally attached) 120 , 1/2 W or more

#1

Do not connect terminators to #1 through #n-1.

RS-422/485
pins on the

CX

#2

#n
(#n
32)

Terminator (externally attached)

Host

computer

SG

RDB( + )

RDA( - )

SDB( + )

SDA( - )

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

The following diagram illustrates the case when the host computer’s interface is RS-232.

Terminator (externally attached) 120 , 1/2 W or more

#1

Do not connect terminators to #1 through #n-1.

RS-422/485
pins on the

CX

#2

#n
(#n
32)

Terminator (externally attached)

SHIELD

RD( + )

RD( - )

TD( + )

TD( - )

FG

SG

RD B

RD A

SD B

SD A

Host

computer

Converter

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

FG

SG

RD B

RD A

SD B

SD A

(SG)

(RD B)

(RD A)

(SDB)

(SDA)

RS-232