background image

4-16

IM 04L31A01-17E

4.6

Modbus Slave Error Responses

Message Format for Errors

If an invalid command other than those determined as communication error is found in
the message, the CX does not process the message and returns a message in the
following format.

Slave Address

Function Code

Error code

Error Check

Response Error Codes

The meaning of the error codes in error messages is shown below.

Error Code

Meaning

Reason

01

Function code error

The function code does not exist.

02

Register address error

Address outside the range was specified.

03

Register number error

Number outside the range was specified.

07

Not executable

Data to be written is outside the range, etc. The process
specified by the function code cannot be executed due to
reasons other than error codes 01 to 03.

When Responses Are Not Received

If there is no response when a message is sent, the possible reasons are as follows:
• Transmission error is detected (overrun, framing, parity, or CRC-16 error).
• The slave address of the command message is incorrect.
• The spacing of the data constructing the message is greater than 1 s.
• The command message is a broadcast request (slave address set to 00).
Provide a timeout procedure on the communication function or communication program
of the Modbus master to handle the above situation.