6.13 Output Commands (Control)

FJ

Outputs program pattern
information that is currently in
execution.

Syntax

FJ<terminator>

Example

FJ

Description Outputs program pattern information that is

currently in execution. If a program pattern is not

currenly in execution, information about the last

pattern that was executed at the time of

termination is output. In this case, the remaining

segment time (SEGTM) and wait time of wait

action (WAITTM) are zeroes. For details, see

“Output of Program Pattern Information Currently

in Execution” in section 7.2, “ASCII Data Output

Format.”

FK

Outputs PV event/time event
information.

Syntax

FK p1<terminator>
p1: Program parameter numbers (1–30)

1–30: pattern number 1 to pattern number 30

When omitted, assumes the pattern numbers

designated on the CX.

Example

Outputs the status of pattern number 2’s

program operation mode

FK2

Description • Outputs the status of the current PV event and

time event when program operation is in

progress. When program operation is not in

progress, zeroes are output for the statuses of

the PV event and time event.

• The statuses of the PV event and time event

are output separately. The status is indicated

using 32 bits that are divided into 4 groups of

8 bits.

xxx.xxx.xxx.xxx (PV event)

yyy.yyy.yyy.yyy (Time event)

For details, see “Output of PV Event and Time

Event Information” in section 7.2, “ASCII Data

Output Format.”

FN

Output of DI/DO data and internal
switch status

Syntax

FN<terminator>

Example

FN

Description • Outputs the status of control DIO, expansion

DIO (CX2000), and internal switches.

• Outputs the status of control DIO, EXTDIO

(CX2000), and internal switches in binary.

For the output format, see section 7.3, “DI/DO

Data and Internal Switch Status” under

“Output Format of BINARY Data.”

FO

Output of status of DIO operation
monitoring function

Syntax

FO<terminator>

Example

FO

Description Outputs the status of the DIO monitoring function

in binary. For the output format, see section 7.3,

“DIO Monitoring Function Status” under “Output

Format of BINARY Data.”

FW

Output of pattern numbers,
operation status, and loops
assigned to patterns

Syntax

FW<terminator>

Example

FW

Description Outputs pattern numbers, operation status, and

loops assigned to patterns in binary. For the

output format, see section 7.3, “Output of Pattern

Numbers, Operation Status, and Loop Numbers

Assigned to Patterns” under “Output Format of

BINARY Data.”

DQ

Outputs the SP number and PID
number of external loops

Syntax

DQ p1<terminator>
p1: Loop numbers (1–12, or 1–4 on the

CX1000)

Query

DQ?

Example

Outputs the SP and PID number of loop number

2.

DQ2

Description With the selected external loop, the currently

used SP number and PID numbers are output.

DR

Output of control mode of
external loops

Syntax

DR p1<terminator>
p1: Loop numbers (1–12, or 1–4 on the

CX1000)

Query

DR?

Example

Outputs the control mode of loop number 2.

DR2

Description The status of the control mode of the selected

external loop is output. The status of each of 32

bits, delimited in groups of 4, is displayed every 8

bits.

xxx.xxx.xxx.xxx

For details, see section 7.2, “Control Mode

Output” under “Output Format of ASCII Data.”