Ascii output, Binary output, Ascii output -2 binary output -2 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 194

Advertising
background image

7-2

IM 04L31A01-17E

ASCII Output

The following types of ASCII data are available. For a description of the data formats,
see section 7.2.

Setting/basic setting data, decimal point position/unit information, measured/
computed/control data, SP number and PID number, control mode, program operation
mode, program pattern information that is currently in execution, PV event/time event
information, status of the program control end signal, communication log, FTP log,
operation error log, key login log, Web operation log, e-mail log, alarm summary,
message summary, status information, file list, data list, and user level

Syntax

EA

CRLF

...............

CRLF

:

...............

CRLF

...............

CRLF

EN

CRLF

BINARY Output

Conceptual Diagram

'E'

'B'

BINARY Data

ASCII

BINARY

Data length

Data sum

Flag ID Header

sum

1 byte

BINARY header
(12 bytes)

BINARY data

BINARY data
(2 bytes)

CR

LF

EBCRLF

Indicates that the data is BINARY.

Data Length

The byte value of “flag + identifier + header sum + BINARY data + data sum.”

Header Sum

The sum value of “data length + flag + identifier.”

BINARY Data

For details on the output format of various data types, see section 7.3.

Data Sum

The sum value of “BINARY data.”

Note

The data length of the BINARY header section is output according to the byte order specified
with the BO command.

7.1 Response Syntax