Control mode output, Control mode output -11 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 203

Advertising
background image

7-11

IM 04L31A01-17E

7

Response

Control Mode Output

• Output data using an FM command for internal loops, or a DR command for external

loops..

• The status of the control mode of the selected loop is output. The status is indicated

using 32 bits that are divided into 4 groups of 8 bits.

Syntax

EA

CRLF

xxx.xxx.xxx.xxx

CRLF

EN

CRLF

xxx

The statuses of bits 31 to 24, 23 to 16, 15 to 8, and 7 to 0 are indicated
in order in decimal notation.

Bit 31

0

1

2

3

4

• The status of each bit indicates the status of each control mode.

Bit 0 status

0: stop, 1: run

Bit 1 status

0: local, 1: remote

Bit 2 status

0: auto, 1: manual

Bit 3 status

0: Not in cascade (cas) control
1: In cascade control

Bit 4 status

0: Not auto tuning (AT)
1: Auto tuning

Bit 31 status 0: Not in program operation, 1: In program operation

• When bit 3 is 1 (in cascade control), the secondary loop of the

cascade can be in any of the statuses auto, manual, or cas. The
primary loop of the cascade is fixed to auto.

Example

When in program operation, auto tuning, in cascade control, auto, remote, and run.

EA

128.000.000.027

EN

7.2 Output Format of ASCII Data