5 communications as a modbus slave, Command message construction, Specifying the register number – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 107

Advertising
background image

4-13

IM 04L31A01-17E

4

Modbus Protocol

4.5

Communications as a Modbus Slave

This section explains the command messages used when setting the CX to Modbus
slave and communicating with a Modbus master device. By sending a command
message from a Modbus master device, the input registers of the CX can be read and
the hold registers can be read or written.

Command Message Construction

Below is the construction of command messages sent from a Modbus master device to
the CX.

Slave Address

Function Code

Data

Error Check

Slave Address

Specify the address of the Modbus slave device to communicate with. The slave
address on the CX is set in the range of 1 to 32 (selected in the serial interface
settings). The command messages from a master device are received by all the
Modbus slave devices that are connected. However, only the slave device with the
matching address reads the message and returns data.

Function Code

Specifies the command (function code) from the Modbus master.

Data

Specifies parameters such as the internal register (D register) number and quantity
according to the function code.

Error Check

Error check is performed using cyclic redundancy check (CRC-16).

Specifying the Register Number

Following the function code, data that is required by the Modbus slave device in
executing the function is transmitted. The data includes the register number to which a
read or write operation is to be executed.

The following table shows the assignment of the reference number to each register on
the CX.

Item

Reference Number

Input register

3xxxx

Hold register

4xxxx

If the Modbus master device is to specify the input register or the hold register using a
command message, the register is specified using a relative number with respect to the
reference number. If the reference number of the item to be specified is 4xxxx, the
relative number with respect to this reference number is the number obtained by
subtracting 40001 from 4xxxx. For example, if the reference number of the input register
to be specified is 30100, the relative number is 99.

Reference Number

Relative Number

30100

30100–30001 = 99

Note

For information on the contents of the input registers and hold registers, see appendix 6.

Advertising