Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 187

Advertising
background image

6-58

IM 04L31A01-17E

MI

Outputs display data and event
data in the internal memory

Syntax

MI p1,p2,p3,p4<terminator>
p1: Operation type

DIR

Put the data on standby for

communication output and output

data list

GET

Output (first time)

NEXT

Output (succeeding times). This

parameter is used to output the

remaining data when the first

output operation is not adequate.

RESEND Retransmit the previous output

SIZE

Output the data size (capacity)

p2: Output data type

DISPLAY

Display data

EVENT

Event data

p3: Block number (1 to 16)

p4: Output format (FILE, DATA)

Example

Output the data in block number 1 containing

display data using the file output format.

MIGET,DISPLAY,1,FILE

Description • Parameter p2 is valid when p1 is set to DIR,

GET, or SIZE.

• Parameters p3 and p4 are valid when p1 is

set to GET or SIZE.

• This command can be used to output data

over the communication interface (Ethernet or

serial) that was selected with the XO

command.

• This command outputs the data, which have

been put on standby using (p1=) DIR, using

(p1=) GET. Make sure to put the data on

standby using DIR before outputting the data

using GET.

MO

Outputs TLOG data, manual
sample data, and report data in
the internal memory

Syntax

MO p1,p2,p3<terminator>
p1: Operation type

DIR

Put the data on standby for

communication output and

output data list

GET

Output (first time)

NEXT

Output (succeeding times).

This parameter is used to

output the remaining data when

the first output operation is not

adequate.

RESEND

Retransmit the previous output

SIZE

Output the data size (capacity)

p2: Output data type

TLOG

TLOG data

MANUAL

Manual sampled data

REPORT

Report

p3: Block number

When p2 is set to TLOG

1 to 16

When p2 is set to MANUAL

1 to 50

When p2 is set to REPORT

1 to 40

Example

Output the data in block number 1 containing

TLOG data from the CX.

MOGET,TLOG,1

Description • Parameter p2 is valid when p1 is set to DIR,

GET, or SIZE.

• Parameter p3 is valid when p1 is set to GET

or SIZE.

• This command can be used to output data

over the communication interface (Ethernet or

serial) that was selected with the XO

command.

• This command outputs the data, which have

been put on standby using (p1=) DIR, using

(p1=) GET. Make sure to put the data on

standby using DIR before outputting the data

using GET.

6.11 Output Commands (Setup, Measurement, and Computation Data Output)