Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 253

Advertising
background image

9-20

IM 04L31A01-17E

Executing the Auto Setting
(Applicable only to UT Series.)

8.

Use the arrow keys to move the cursor to the [Auto setting] box.

9.

Press the [Execute] soft key.
The detail information (item ID, item name, register address, decimal point
position, and high and low limits of value range) of the tuning parameters of the
connecting model is set automatically.

The detail information is set automatically according to the various information that was
read automatically on the External loop setting (Basic setting) display.)

Note

The [Execute] soft key is used read the detail information of the connecting model automatically.
Use caution because all preexisting detail information will be overwritten.

Turning On/Off the Tuning Parameters

10.

Use the arrow keys to move the cursor to each tuning parameter box.

11

Press the [On] or [Off] soft key.
If you selected [On], the cursor moves to the [Item name] box and the [Detail]
soft key appears. Proceed to step 12.
If you selected the [Off], proceed to step 13.

Setting (Correcting) the Detail Information
(Perform the following procedures only if parameters need to be corrected.)

12.

Press the [Detail] soft key. An entry box appears. Set [Item ID], [Item name],
[Register address], [Decimal point], and [Range lower/upper].

9.6 External Loop Setting > Tuning Setting