Appendix 6 Register Assignments

Register Assignments during Modbus Slave

The register assignments of the Modbus slave function are shown below. On the
CX1000, if you write to or read from a register that does not exist (communication
registers C13 to C30, measurement channels 07 to 20, computation channels 43 to 60,
and control loops 3 to 6), an error (error code 2) is returned.

• Hold Registers

40001-40030
40101

40301

40302

40303

40304

40305
40306
40501

40502

40503

40504

:
40577

40578

40579

40580

Communication register data
Control operation start/stop of all loops

Memory start/stop

Alarm ACK

Computation start/stop

Save the manual trigger, manual sampled,
snapshot, display data to the external
storage medium/saves the event data to
the external storage medium

Write message
Revert to the operation display
Alarm value of measurement channel 1
(Alarm number 1)
Alarm value of measurement channel 1
(Alarm number 2)
Alarm value of measurement channel 1
(Alarm number 3)
Alarm value of measurement channel 1
(Alarm number 4)
:
Alarm value of measurement channel 20
(Alarm number 1)
Alarm value of measurement channel 20
(Alarm number 2)
Alarm value of measurement channel 20
(Alarm number 3)
Alarm value of measurement channel 20
(Alarm number 4)

–32768 to 32767
0: Stop
1: Start
0: Memory stop
1: Memory start
When writing
0: Execute alarm ACK
When reading
0: Alarm not illuminated
1: Alarm illuminated
2: Alarm blinking
0: Stop computation
1: Start computation
2: Reset computation
0: Execute manual sampling
1: Activate manual trigger
2: Snapshot
3: Save display data to the external storage

medium

4: Save event data to the external storage

medium

1 to 8: Message number
0: Set the display back to the operation display
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)
:
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)
Value within the measurement span excluding
the decimal point (see the SA command)

R/W
W

*1

R/W

R/W

R/W

W

*1

W

*1

W

*1

R/W

R/W

R/W

R/W

:
R/W

R/W

R/W

R/W

Modbus Register

Number

Description

Value

Read/Write

*1 If a write-only register in the hold registers is read, a “0” is returned.