Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 291

Advertising
background image

App-32

IM 04L31A01-17E

D1101

D1102
D1103
D1104
D1105
D1106
D1107

D1108
D1109

D1110

D1111

D1112
D1125

D1126

D1127

D1128

D1131-D1142

D1155-D1158

D1161-D1172

PID parameter of
PID number 1 of
loop 1

Control alarm
value of PID
number 1 of loop 1

PID parameter of
PID number 2 of
loop 1
Control alarm
value of PID
number 2 of loop 1
PID parameter of
PID number 3 of
loop 1

Target setpoint (SP)

Proportional band (P)
Integral time (I)
Derivative time (D)
Output low-limit
Output high-limit
Shutdown function enable/disable

Manual reset
Hysteresis value

Hysteresis activation point

Control action direction switching

Preset output
Control alarm value
(Alarm number 1)

Control alarm value
(Alarm number 2)
Control alarm value
(Alarm number 3)
Control alarm value
(Alarm number 4)
Same as the PID parameters of
PID number 1 of loop 1

Same as the control alarm
values of PID number 1 of loop 1

Same as the PID parameters of
PID number 1 of loop 1

Within the measurement span excluding the
decimal point
1 to 9999: 0.1 to 999.9%
0 to 6000
0 to 6000
–50 to 1050: –5.0% to 105.0%
–50 to 1050: –5.0% to 105.0%
0: OFF
1: ON
–50 to 1050: –5.0% to 105.0%
Within the measurement span excluding the
decimal point
0: OFF
1: Upper
2: Lower
0: Reverse
1: Direct
–50 to 1050: –5.0% to 105.0%
Varies depending on the alarm type as
follows:
SP/PV alarm

Within the measurement span excluding
the decimal point

Deviation alarm (high-limit and low-limit)

Within EUS –100.0 to 100.0% of the
measurement span excluding the decimal
point

Deviation alarm (high & low limit and within
high & low limits)

Within EUS 0.0 to –100.0% of the
measurement span excluding the decimal
point

Output alarm

–50 to 1050: –5.0% to 105.0%

(See the AV command)
Same as above

Same as above

Same as above

Same as the range for the PID parameters
of PID number 1 of loop 1

Same as the range for the control alarm
values of PID number 1 of loop 1

Same as the range for the PID parameters
of PID number 1 of loop 1

R/W

R/W
R/W
R/W
R/W
R/W
R/W

R/W
R/W

R/W

R/W

R/W
R/W

R/W

R/W

R/W

R/W

R/W

R/W

D Register

Number

Description

Register Type

Value

Read/

Write

Appendix 6 Register Assignments