Wait action setting, Program initial setting, Program operation parameters – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 150: Event setting, Pt sets the segment time, Pu sets the ramp-rate time unit/ ramp, Pg segment pid group number, Pj sets the segment shifting action and wait, Event setting et sets the time event, Wait action setting pz sets the wait zone

Advertising
background image

6-21

IM 04L31A01-17E

6

Command

PT

Sets the segment time

Syntax

PT p1,p2<terminator>
p1: Segment number (1 to 99)

p2: Segment time (hh:mm:ss fixed format)

hh

Hour (00 to 99)

mm

Minute (00 to 59)

ss

Second (00 to 59)

Set a value greater than or equal to 1 s.

Query

PT[ p1]?

PU

Sets the ramp-rate time unit/
ramp

Syntax

PU p1,p2,p3<terminator>
p1: Segment number (1 to 99)

p2: Ramp-rate time unit (Hour, Minute)

p3: Ramp (ramp per unit time 1 digit to EUS

(100%))

Query

PU[ p1]?

PG

Segment PID group number

Syntax

PJ p1,p2<terminator>
p1: Segment number (1 to 99)

p2: Segment PID group number (1 to 8)

Query

PG[ p1]?

PJ

Sets the segment shifting action
and wait

Syntax

PJ p1,p2,p3,p4<terminator>
p1: Segment number (1 to 99)

p2: Segment shifting action*

p3: Wait (Off/Shift/Within)

p4: Wait zone number (1 to 5) (selectable only

when p3 is set to Shift or Within)

*:Continue/HoldShift/LocalShift/

ResetShift

Query

PJ[ p1]?

Event Setting
ET

Sets the time event

Syntax

ET p1,p2,p3,p4,p5<terminator>
p1: Segment number (1 to 99)

p2: Event number (1 to 16)

p3: Enable/disable event (Off, On1, On2, On3)

p4: On-time (hh:mm:ss fixed format)

hh

Hour (00 to 99)

mm

Minute (00 to 59)

ss

Second (00 to 59)

p5: Off-time (hh:mm:ss fixed format)

hh

Hour (00 to 99)

mm

Minute (00 to 59)

ss

Second (00 to 59)

P5>P4

Query

ET[ p1,p3]?

6.4 Setting Commands (Control)

Wait Action Setting
PZ

Sets the wait zone

Syntax

PZ p1,p2,p3,p4,p5<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Wait zone number (1 to 5)

p3: Wait Off/On

p4: High boundary of the zone (1 digit to EUS

(100.0%))

p5: Low boundary of the zone (1 digit to EUS

(100.0%))

p4 and p5 can be specifed only when p3 is ON.

Query

PZ[ p1,p2]?

PW

Sets the wait time

Syntax

PW p1,p2<terminator>
p1: Wait zone number (1 to 5).

p2: Wait-time setting (hh:mm:ss fixed format)

hh

Hour (00 to 99)

mm

Minute (00 to 59)

ss

Second (00 to 59)

Query

PW[ p1]?

Program Initial Setting
PO

Sets the start setpoint

Syntax

PO p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)

p2: Start target setpoint EU (0.0 to 100.0%)

Query

PO[ p1]?

PQ

Sets the start code

Syntax

PQ p1<terminator>
p1: Start code*

*: StartTargetSP

RampPV1Start

TimePVStart

RampPV2Start

RampPV3Start

RampPV4Start

RampPV5Start

RampPV6Start

Query

PQ?

Program Operation Parameters
PD

Sets the ramp/soak select

Syntax

PD p1,p2<terminator>
p1: Segment number (1 to 99)

p2: Ramp/soak selection (Ramp/Soak)

Query

PD[ p1]?

PM

Sets the final target setpoint

Syntax

PM p1,p2,p3<terminator>
p1: Segment number (1 to 99)

p2: Loop number (1 to 6) (1 or 2 on the CX1000)

p3: Final target setpoint EU (0.0 to 100.0%)

Query

PM[ p1,p2]?