IM 04L31A01-17E

3.6

Automatic Recovery Settings

Explanation

You can select whether or not to automatically recover communications with modbus
mice and temperature meters. If you select automatic recovery, you can also specify the
recovery interval. You can select one of the following intervals: 1 min, 2 min, 5 min, 10
min, 20 min, 30 min, or 60 min.

Procedure

1.

Press the MENU key.
The setting mode (control) display appears.

2.

Press the FUNC key for approximately 3 s.
The basic setting menu appears.

3.

Press the [#7] (Communication) soft key ([#9] (Communication) soft key on the
CX1000).
The communication function setting menu appears.

4.

Press the [#5] (AUX) soft key ([#9] (AUX) soft key on the CX1000).
Communication (AUX) setting display appears.

5.

Use the arrow keys to move the cursor to the [Auto recovery] box.

6.

Press the [On] or [Off] soft key.

Confirming or Canceling the Settings

7.

To confirm the new settings, press the DISP/ENTER key. To cancel the
settings, press the ESC key.

For a detailed procedure in confirming or canceling settings, see “Setup Procedure Using
Operation Keys” on page ix.

Saving the Settings

8.

Press the ESC key several times to display the basic setting menu.

9.

Press the [End] soft key. A dialog box appears for you to select whether to save
the settings.

10.

To save the settings, select [Yes]. To not save the settings, select [No]. To
return to the basic setting menu, select [Cancel]. Then, press the DISP/ENTER
key.