Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 219

Advertising
background image

7-27

IM 04L31A01-17E

7

Response

• Flag

The meaning of the flags are given on the table below. The flags are valid during
FIFO data output. The flags are undefined for other cases.

Flag

Bit

Meaning of the Flag

0

1

7

No

Yes

Indicates that the screen snap shot was executed.

6

5

4

3

2

No

Yes

Indicates that the decimal position or unit information was changed during

measurement.

1

No

Yes

Indicates that the FIFO acquiring interval was changed with the FR command

during measurement.

0

No

Yes

Indicates that the internal process took too much time (computation, for

example) and that the measurement could not keep up at the specified scan
interval.

The bits that have “.” for the flag are not used. The value is undefined.

• Block Member

Name

BINARY Value

Year

0 to 99

Month

1 to 12

Day

1 to 31

Hour

0 to 23

Minute

0 to 59

Second

0 to 59

Millisecond

0 to 999

(Reserved)

Undefined

Measurement/computation/control

00H: measurement/control, 80H: computation

Channel

01 to 248

Alarm status*

A1
A2

0 to 31

A3
A4

* BINARY value 0 to 31 is entered using a byte for the alarm status. The binary values 0 to 31

correspond to the alarm types of H (high limit alarm), L (low limit alarm), h (difference high-limit
alarm), l (difference low-limit alarm), R (high limit on rate-of-change alarm), r (low limit on rate-of-
change alarm), T (delay high limit alarm), t (delay low limit alarm), PVH (PV high-limit alarm), PVL
(PV low-limit alarm), DVH (deviation high-limit alarm), DVL (deviation low-limit alarm), DVO
(deviation high & low limit alarm), DVI (deviation within high & low limits alarm), SPH (SP high-
limit alarm), SPL (SP low-limit alarm), OTH (output high-limit alarm), OTL (output low-limit alarm),
ETC (other alarm), and space (no alarm) as follows:
0: no alarm, 1: H, 2: L, 3: h, 4: l, 5: R, 6: r, 7: T, 8: t, 21: PVH, 22: PVL, 23: DVH, 24: DVL, 25:
DVO, 26: DVI, 27: SPH, 28: SPL, 29: OTH, 30: OTL, 31: ETC.

Special Data Values

The measured/computed/control data take on the following values under special
conditions.

Special Data Value Type

Measured/Control data

Computed data

+ Over

7FFFH

7FFF7FFFH

– Over

8001H

80018001H

Skip

8002H

80028002H

Error

8004H

80048004H

Undefined

8005H

80058005H

Note

The number of blocks, number of bytes, and measured/computed/control data are output
according to the byte order specified with the BO command.

7.3 Output Format of BINARY Data

Advertising