Modbus Protocol

4.4

Checking the Operation Status of the Modbus
Master Function

Explanation

”MODBUS STATUS” Display

You can check the operation status of the Modbus master function on the “MODBUS
STATUS” screen.

CX2000 screen example

Address and register
number of the slave
device

Communication input
channel

Detail code

Status lamp

Communication condition

Communication Status

The communication status is displayed using the status lamp and the detail code.

Status Lamp

Detail Code

Meaning

Green

GOOD

Communication is operating normally.

Yellow

Retrying.

Red

Communications stopped since communications did not recover
after the specified number of retrials.

NONE

No response from the slave device.

FUNC

The slave device cannot execute the command from the CX.

REGI

The slave device does not have the specified register.

ERR

There is an error in the response data from the slave device.

(Space)

The detail code is not displayed until the status is confirmed
when communication is started.

Resuming Command Transmission

You can use the front panel keys to resume command transmission to the slave
device to which command transmission is stopped.

Data during Retrial and When Communication Is Stopped

The communication input data is held at the previous value during retrial. When
command transmission is stopped, communication input data becomes error data. In
this case, computation channels display “+******.”

Data Dropout

Data drop occurs when the commands from 1 to 8 do not complete within the read
cycle (see appendix 5). When a data dropout occurs, the communication input data is
held at the previous value. Take measures such as making the read cycle longer or
reducing the number of commands.