Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 123

Advertising
background image

2-6

IM 04L31A01-01E

LOOP2

2

1

3

2

1

PV

PV

(RSP)

(RSP)

(RSP)

(RSP)

PV

PV

PV1

PV1

PV2

PV2

LOOP1

• 2 loops

PV, PV1, PV2: PV input, (RSP): RSP input
(not used during program control), : unused terminal

During single-loop control

During cascade control

During loop control with
PV switching

[Control mode setting]

When PV/SP is ON, the numbers CI01, CI02, CI03, CI04, CI05, CI06, CI07, CI08, CI09,
and CI10 are assigned to each control input terminal starting on the right as you face the
terminals, and the PV/SP of each loop is the computed value.

Terminal Arrangements of the Control Output Terminal Block
Each block has a control output containing 2 loops of current output, voltage pulse
output, and relay contact output terminals, 6 contact input, 2 relay contact output, and 4
transistor output terminals. The following figure shows their arrangement. Wire the
terminals according to the configuration.

LOOP1

NO
NC

C

NO

C

2

NO
NC

C

LOOP2

CTRL OUT

mA

PULS

C

LOOP2

mA

PULS

C

C

5
6

C

3
4

4
5
6

1
2
3

LOOP1

CTRL OUT

DIGITAL OUT

DIGITAL OUT

DIGITAL IN

NO

C

1

LOOP3

NO
NC

C

NO

C

2

NO
NC

C

LOOP4

CTRL OUT

mA

PULS

C

LOOP4

mA

PULS

C

C

C

4
5
6

1
2
3

LOOP3

CTRL OUT

DIGITAL IN

NO

C

1

LOOP5

NO
NC

C

NO

C

2

NO
NC

C

LOOP6

CTRL OUT

mA

PULS

C

LOOP6

mA

PULS

C

C

C

4
5
6

1
2
3

LOOP5

CTRL OUT

DIGITAL IN

NO

C

1

DIGITAL OUT

DIGITAL OUT

DIGITAL OUT

DIGITAL OUT

• For loops

1 and 2

• For loops

3 and 4

• For loops

5 and 6

Control power supply
voltage pulse output

Contact
input

Transistor
output

Relay contact
output

Control relay
contact output

C: Common
NO: Normally

Opened

NC: Normally

Closed

mA: Current

output

PULS: Voltage pulse output

5
6

3
4

5
6

3
4

[DIGITAL OUT] terminals 1 to 6 are indicated using the following numbers when the
control output terminal block is selected in the contact (relay) output registration setting
or alarm relay output setting.
• DO001 to DO006 (Contact output of the loop 1 and 2 control output terminal block [CTRL1-2])
• DO101 to DO106 (Contact output of the loop 3 and 4 control output terminal block [CTRL3-4])
• DO201 to DO206 (Contact output of the loop 5 and 6 control output terminal block [CTRL5-6])
In addition, [DIGITAL IN] terminals 1 to 6 are indicated using the following numbers when
the control output terminal block is selected in the contact input registration setting.
• DI001 to DI006 (Contact output of the loop 1 and 2 control output terminal block [CTRL1-2])
• DI101 to DI106 (Contact output of the loop 3 and 4 control output terminal block [CTRL3-4])
• DI201 to DI206 (Contact output of the loop 5 and 6 control output terminal block [CTRL5-6])

Note

In the contact (relay) output setting, relay contact outputs DO001, DO002, DO101, DO102,

DO201, and DO202 and the numbers of transistor outputs are not distinguished. Confirm this

before registering the output signals.

2.3 Wiring