Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 85

Advertising
background image

1-73

IM 04L31A01-01E

Explanation of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Setting Groups

The control monitoring data and measured/computed data on the operation display are
shown in groups. Therefore, control loops and measurement channels must be
assigned to groups.
Setting Control Groups (for the Control Function)
Up to 6 loops can be assigned to each group. There are eight groups in which external
loops (loops of externally connected controllers) can also be registered. You can assign
a group name for each group.
Setting Measurement Groups (for the Measurement Function)
Measurement channels or computation channels are assigned. Up to 10 groups can be
registered. The groups are common to the trend, digital, and bar graph displays.
On the trend, digital, and bar graph displays, the displayed groups can be automatically
switched at “5 s,” “10 s,” “20 s,” “30 s,” or “1 min” intervals.
For trend display, the waveform of all applicable channels can be displayed on a single
display rather than in groups.

Displaying Tags

For identifying the control loops and channels, tags (tag comments can also be assigned
to control loops) can be displayed in place of numbers.

Control Operation Display > Control Group Display

Target setpoint (SP)
Red:

Can be set

Yellow: Cannot be set

Loop selection
cursor

Auto/manual

Tag name

PV input value

*

Target setpoint

*

Control output value

*

Remote (REM) or local (LOC)

Operation running (RUN), operation stopped (STP),
or auto tuning (blinking AT)

Alarm mark

PV input value
Upper limit alarm
Red: Alarm

occurrence

Green: Alarm OFF

Control output value (OUT)
Red: Controllable
Yellow: Not controllable

Scale
(The value indicates span lower
limit or upper limit.)

Process value (PV)
Red: Alarm

occurrence

Green: Alarm OFF

Tag comment
display section

*

Red when alarm

is occurring

DIO operation monitoring function

Analog retransmission

When monitoring
only DI or DO

Displayed using the
specified color when
DO or DI is ON

Displayed using the
specified color when
DO or DI is OFF

Displayed using the
specified color when
DO is ON

Displayed using the
specified color when
DO is OFF

When monitoring
both DI and DO

Displayed using the
specified color when
DI is ON

Displayed using the
specified color when
DI is OFF

Output value

Tag

Tag comment

Label for ON

Label for OFF

1.16 Display Function