Operations during Control Operation

6

Display and Operation on the Control Display and Control Mode
For internal loops, the information that is displayed in the control data display section
(“Dsp.” in the following table) and the possible switching/setting operations (“Opr.” in the
following table) vary depending on the control mode as shown in the following figure.
For a description on the “control mode and switching operation” of external loops through
the optional Green series communications, see the DAQSTATION CX1000/CX2000
Communication Interface User’s Manual

.

MODE: Auto (AUT), manual (MAN), or cascade (CAS)

REM/LOC: Remote or local (PRG/LOC: Program or local*

3

)

RUN/STP: Operation running (RUN) or operation stopped (STP)

SP: Target setpoint

OUT: Control output

Dsp.

Yes

Yes*

2

Yes

Yes

Opr.

Yes

No

Yes

Yes

Opr.

Yes*

1

Yes*

1

No

Yes*

1

Control Mode

Operation Status/

Switching

Single loop

Cascade

PV switching

Primary

Secondary

Dsp.

Yes

Yes

No

Yes

Dsp.

Yes

No

Yes

Yes

Opr.

Yes

No

Yes

Yes

Dsp.

Yes

Yes

Yes

Yes

Opr.

Yes

Yes

Yes

Yes

Dsp.

Yes

Yes

Yes

Yes

Opr.

Yes

No

Yes

Yes

MODE

REM/LOC*

3

RUN/STP

SP

OUT

*1 Not displayed on the soft key menu if [Remote setting] and [Program control] are set to

[Off].

*2 Fixed to auto (AUT).
*3 “PRG/LOC” when [Program control] is [On].

In addition, the following table shows the conditions in which the soft key menu for
switching/setting appears, but operation is not possible.

Switching/Setting Operation

Condition in Which Operation

Corrective Action

Is Not Possible

Switching to [CAS] using

When “A/D error”, “burnout error”,

Resolve the cause of error on

[MODE]

or “Computation Error”* occurs at

on the primary loop

the PV input or remote input of
cascade control the primary side

Switching to [REM] using

When “A/D error”, “burnout error”,

Resolve the cause of error at

[REM/LOC]

or “Compuration Error”* the

occurs at the remote input.

remote input

Switching to [PRG] using

When program control is in

Switch to [RUN] of program

[PRG/LOC]

reset mode

control

Changing [SP]

During auto tuning, remote mode,

Stop auto tuning, switch to

program mode, or cascade control

local mode, or switch to auto/

(when [MODE]of the secondary

manual operation

loop is [CAS])

Changing [OUT]

When the operation is stopped or

Switch to manual operation

when operation mode is not
manual ([MODE] is not [MAN])

* When the computation of the loop specified in PV/SP computed results in an error.

• Error messages for the operations above

Switching to [CAS] using [MODE]:

Cascade mode cannot be selected.

Switching to [REM] using [REM/LOC]: Remote mode cannot be selected.
Switching to [PRG] using [PRG/LOC]: Program mode cannot be selected.
Changing [SP] or [OUT]:

Can not operate in the present situation.

6.1

Operations on the Control Group Display (Switching Displayed Information and Control Operation Modes)