Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 89

Advertising
background image

1-77

IM 04L31A01-01E

Explanation of Functions

3

2

1

4

5

6

7

8

9

10

11

12

13

14

Control Operation Display > Trend Display

Displayed Information and Display Direction
In addition to the waveforms of measured/computed data, PVs, SPs, and OUT of
internal/external control loops are also assigned to channels and displayed. The display
direction of the waveform can be set to horizontal or vertical as show in the following
figure. Numeric values can be displayed along with waveforms.

Note

For a description of the assignment of internal control channels (internal loop channels) and external

control channels (external loop channels), see channel assignment explanation on

page 1-89

.

Trend (Horizontal) Display

Channel No. or
tag name

Measured or
computed value
Unit

Specified
alarm

Needle
(displayed
using the
channel
display color)

This area is
displayed
using the
channel
display color.

Message (message mark, time, and message)

Trip line

Grid

Waveform (displayed using the channel display color)

Scale

Time

Display update rate

Type 1

Type 2

Numerical

display section

Trend (Vertical) Display

Scale

Display update rate

Waveform (displayed using
the channel display color)

Needle (displayed using the channel display color)

Trip line

Unit

This area is also displayed using
the channel display color.

Message (message mark,
time, and message)

Channel No. or
tag name

Time

Numerical display
section

Specified alarm Measured or computed value

Grid

Displayed Information

Description

Message

Messages specified by the user can be displayed at arbitrary points in time. For example, by
displaying a message when a certain operation is carried out, the point at which the operation is
carried out can be seen visually. Displayed messages are saved.

Trip line

You can display a line to indicate a particular value of interest (trip line) for each group. You can
select the thickness of the displayed line from three types: 1, 2, or 3 dots. Up to four trip lines can
be displayed on a single group.

Scale

A scale appropriate for the measured item can be displayed for each channel. The number of
divisions of the display scale created by the main scale marks can be set to a value in the range 4
to 12 divisions (also applies to the bar graph display). Medium and small scale marks are
displayed in between the main scale marks. You can select whether or not to display the scale
for each channel and the display position.

1.16 Display Function