Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 229

Advertising
background image

6-4

IM 04L31A01-01E

Switching between Remote and Local Modes

The soft key menu does not show [REM/LOC], if [Control] > [Contact input-
registration/AUX(Alarm mode...] > [Remote setting] is set to [Off]. Remote input
cannot be used for the SP when the secondary loop of cascade control is selected or
during program control. Thus, there is no remote/local switching in these cases.
1. Use the

arrow keys

to move the cursor to the desired control loop.

2. Press the

[REM/LOC] soft key

.

A pop-up window for switching between remote and local appears.

Window for switching between
remote and local

3. Select [REMOTE] or [LOCAL] using the

up and down arrow keys

.

4. Press the

DISP/ENTER key

to confirm the changes.

To close the window without making any changes, press the ESC key.

Switching between Program and Local Control (only on models with the program
control option)

The soft key menu does not show [PRG/LOC] if [Program control] is set to [Off].
1. Use the

arrow keys

to move the cursor to the desired control loop.

2. Press the

[PRG/LOC] soft key

.

A pop-up window for switching between program and local appears. The window
shows the current control output.

Window for switching between
program and local

3. Select [PROGRAM] or [LOCAL] using the

up and down arrow keys

.

4. Press the

DISP/ENTER key

to confirm the changes.

To close the window without making any changes, press the ESC key.