1.10 Control Alarm Related Settings

Alarm Operating Conditions (Alarm Mode)

The following three types of alarm operating conditions are available for selection.
• Alarm is always enabled ← initial value
• Alarm is disabled when operation is stopped.
• Alarm is disabled when operation is stopped or during manual (MAN) operation mode.

Alarm Type

You can select the alarm type from the following.

Alarm

setpoint

Close

Hysteresis

PV

Open

Close

Hysteresis

Open

Hysteresis

Open

SP

Deviation
setpoint

Close

Open

Hysteresis

Close

Alarm action

(Open/close: relay contact status)

Alarm action

(Open/close: relay contact status)

Alarm type

Alarm type

Hysteresis

Hysteresis

Close

Open

Close

Deviation

setpoint

Hysteresis

Hysteresis

Open

Open

Close

Alarm setpoint

Setpoint

Hysteresis

Hysteresis

Alarm setpoint

Setpoint

Hysteresis

Alarm setpoint

Output

value

Hysteresis

Alarm setpoint

PV high-limit

PV low-limit

Deviation
high-limit

Deviation
low-limit

Deviation
high & low
limit

PV

PV

Alarm

setpoint

SP

Deviation
setpoint

Deviation
setpoint

Deviation within
high & low
limits

SP high-limit

SP low-limit

Output high-limit

Output low-limit

Output

value

SP

PV

PV

PV

SP

Action When an Alarm Occurs

Alarms can be generated at the contact output and on the CX2000 display.
The alarm contact output can be assigned to the [DIGITAL OUT] terminal (see page 2-6) of the
control output terminal block and the control DIO expansion terminal block.
The alarm display can be confirmed by the mark on the control group displays, alarm occurrence
history on the alarm summary display, and the alarm icon on the operation status display section.

Note

The CX2000 has measurement alarms (see section 1.15, “Measurement Function >

Measurement Alarm Related Settings”) in addition to the control alarms. The measurement

alarms can also be output at the contact output and on the display. Measurement alarms

can be output from the [DIGITAL OUT] terminal of the control output terminal block and the

control DIO expansion terminal block and the [ALARM] terminal of the measurement alarm

option terminal block. In terms of displays, the measurement alarms are displayed along

with control alarms on the alarm summary display. The alarm icon on the operation status

display section is shared with control alarms (indicator hold behavior is also common).

You cannot assign the control alarm output to the [ALARM] terminal of the measurement

alarm option terminal block.