Square-root computation of pvs – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 36

Advertising
background image

1-24

IM 04L31A01-01E

Ten-segment linearizer
approximation

Input

(a)

Output

(b)

Square-root Computation of PVs

The square-root function is used in the case such as when the differential pressure
signal of a restriction flowmeter such as an orifice or a nozzle is converted to a flow
signal. You can also set the low-signal cutoff point for the square-root computation.
Square-root computation ON/OFF setting: ON or OFF (the initial value is 1.0%)
Selectable range of the low-signal cutoff of the analog input: 0.0 to 5.0% (the initial value
is OFF)

100.0%

Input

100.0%

0.0%

Slope: 1

Low-signal

cutoff point

(0.0 to 5.0%)

PV Range Conversion (only during loop control with PV switching)

The PV range conversion is a function used to determine the PV range of the control
function when the measurement range of the two input signal is different for the loop
control with PV switching. For example, if the input range of the first input is 0 °C to 500
°C and the input range of the second input is 300 °C to 1000 °C, the PV range
conversion is used to convert the PV range of the control function to 0 °C to 1000 °C.

PV range

0

300

500

1000 °C

PV range of PV input 2

PV range of

PV input 1

1.4 PV Input Related Settings