9 program pattern settings > event output settings, Event output settings -12, 9 event output settings – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 221

Advertising
background image

5-12

IM 04L31A01-01E

5.9

Event Output Settings

This section explains the setting procedure for event output during program control and
program pattern end signaling.

Procedure

Opening the Setting Display

Press the keys in the following sequence:

MENU key

(switch to setting mode(control)) >

#7 soft key

(select [Program-control

parameters] >

#2 soft key

(select [Event output setting])

The following display appears.

Setup Procedure

1.

Use the

arrow keys

to move the cursor (blue) to the item box you wish to

change.
A soft key menu is displayed at the bottom of the display.

2.

Press the

soft key

corresponding to the value you wish to select.

The box for the item you changed turns yellow, and the cursor moves to the next
item box.

3.

Repeat steps 1 and 2 to change the value of all the items you wish to change.

4.

Press the

DISP/ENTER key

to confirm the changes.

The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.