• Delay lower limit alarm

An alarm occurs when the measured/computed value remains below the alarm value
for the specified time (delay).
Delay upper limit alarm example (T is the specified delay)

Alarm release

Alarm occurrence

T

X1

X2

X3

X4

T1

Measured value or
computed value

Alarm setting

• Alarm does not occur at T1, because the time is shorter than the specified delay (T).
• The input exceeds the alarm value at X2, but the alarm occurs at X3 at which the

specified delay period elapses (the time when the alarm occurs is the time at X3).

• The input falls below the alarm value at X4 and the alarm is released.

Note

The following special operations are available for the delay upper/lower limit alarm.

When a delay alarm is set on a computation channel and the computation is stopped

If the computation is stopped in a condition in which the computed value is exceeding the

alarm setting, the alarm is turned ON after the specified period (delay period) elapses.

Alarm occurrence

T

Computed
values

Stop computation

Alarm setting

Delay alarm when a power failure occurs

Alarm detection is reset upon a power failure. It restarts the operation after the power recovers.

Power failure
occurrence/recovery

Power failure
occurrence/recovery

T

T

T

Alarm

On

Off

On

Off

On

Off

Measured value or
computed value

Alarm setting

:Off

Operation when the alarm setting is changed

• When a new delay alarm is set

The alarm detection starts at the time the alarm is set. It is unaffected by the conditions

existing before the alarm is set.

• If the alarm setting of a preexisting delay alarm is changed

• If an alarm is not occurring at the time of the change, alarm detection starts at the

new setting.

• If an alarm is occurring at the time of the change and the alarm type is set to delay

upper limit alarm, the alarm continues as long as the input is above or equal to the

new setting. If the input is below the new setting, the alarm turns OFF. If the alarm

type is set to delay lower limit alarm, the alarm continues as long as the input is

below or equal to the new setting. If the input is greater than the new setting, the

alarm turns OFF.

1.15 Measurement Function > Measurement Alarm Related Settings