Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 236

Advertising
background image

6-11

IM 04L31A01-01E

Operations during Control Operation

6

Setup Items

Manual Tuning
Set the parameters to be tuned using [Control] > [Turning setting]. For the procedure,
see section 4.5, “Control > Tuning setting.”
The initial settings of the tuning parameters are shown below. The numbers indicate the
order of items on the tuning display starting from the upper left corner. The characters
indicate the item names (tuning parameter name). In addition to the tuning parameters
below, [DR] (control direction) and [H] (relay hysteresis) are available. For external loops
using Green Series communications, [DB] (dead band) is also available.

01: SP (target setpoint)

08: D (derivative time)

15: Off

02: A1 (alarm value1)

09: OH (output high-limit)

16: Off

03: A2 (alarm value 2)

10: OL (output low-limit)

17: Off

04: A3 (alarm value 3)

11: MR (manual reset)

18: Off

05: A4 (alarm value 4)

12: PO (preset output)

19: Off

06: P (proportional band)

13: Off

20: Off

07: I (integral time)

14: Off

21: Off

Display and Operation on the Tuning Display and Control Mode
For internal loops, the possible operations that you can perform on the tuning display
vary depending on the control mode.
The table below shows the relationship between the display/operations specific to the
tuning display and the control mode. For the relationship between the display/operations
that are common with the control display and the control mode, see “Display and
Operation on the Control Display and Control Mode” on page 6-6. For a description on
the “display/operations and control mode” of external loops through the optional Green
series communications, see the DAQSTATION CX1000/CX2000 Communication
Interface User’s Manual

.

AT: Execute auto tuning
SP NO.: Switch the SP number
Group NO.: Switch the PID number of the tuning parameter to be manipulated

Dsp.

Yes

Yes

Yes

Yes

Opr.

Yes*

Yes*

Yes*

Yes*

Opr.

Yes

Yes

Yes

Yes

Control mode

Display/Operation

Type

Single loop

Cascade

PV switching

Primary

Secondary

Dsp.

Yes

Yes

Yes

Yes

Dsp.

Yes

Yes

Yes

Yes

Opr.

Yes

Yes

Yes

Yes

AT

SP NO.

GROUP NO.

* Not displayed in the soft key menu if [Control] > [#1 Control

action, Input setting] > [Auto tuning] is set to [OFF].

In addition, there are conditions in which certain soft keys appear, but their operation is not
possible. The table below shows the conditions and corrective action specific to the tuning
display. For the conditions and corrective actions that are common with the control display,
see “Display and Operation on the Control Display and Control Mode” on page 6-6.

Condition in Which Operation Is Not Possible

Corrective Action

When auto tuning is already in progress

Abort the auto tuning operation in
progress.

Mode other than auto operation mode and loop other than

Switch the auto operation mode

the primary loop of cascade control
Primary loop of cascade control and the secondary loop

Switch to cascade mode

are not set to cascade mode
Operation stopped

Start the Operation

When “A/D error” or “burnout error” occurs at the input.

Resolve the cause of the error

• Error messages for the operations above

When auto tuning is in progress: Auto-tuning is activated already.
Others: Auto-tuning cannot be activated.

6.3 Tuning Operation