Setup Item

DIO Operation Monitoring Function Settings

• DIO Operation Monitoring Number

You can enter settings for each DIO monitoring number. There are 36 DIO monitoring
numbers.

• DIO Types

Select the DIO monitoring method. There are 7 types of DIO available.
DI-1:

Displays the input status of the specified DI. The status of the internal
switches are output.

DO-1:

The status of the internal switches is output to 1 DO. 1 (ON) is output when
the internal switches are ON, and 0 (OFF) is output when they are OFF.

DO-2:

You can output the ON and OFF statuses of the internal switches to
separate DOs. 1 (ON) is output from the ON output DO when the internal
switches are ON, and 0 (OFF) is output from the OFF output DO when they
are OFF. 0 (OFF) is output from the ON output DO when the internal
switches are OFF, and 1 (ON) is output from the OFF output DO when they
are ON.

DIO-11: The same operation as the DO-1 is performed while displaying the input

status of the specified DI.

DIO-12: The same operation as the DO-2 is performed while displaying the input

status of the specified DI.

DO-2P: You can output the ON and OFF statuses of the internal switches to

separate DOs. A pulse signal having a 1 to 2 second pulse width is output
from the ON output DO when the internal switches are ON, and from the 0
(OFF) output DO when they are OFF.

DIO-12P:The same action as the DO-2P is performed while displaying the input

status of the specified DI.

Internal switches

ON

OFF

1 (ON)

0 (OFF)

1 to 2 seconds

1 to 2 seconds

1 (ON)

0 (OFF)

1(ON)

0 (OFF)

1 (ON)

0 (OFF)

1 (ON)

0 (OFF)

DO-1/
DIO-11

DO-2/
DIO-12

DO for ON
output

DO for ON
output

DO for OFF
output

DO for OFF
output

DO-2P/
DIO-12P

• SW Number

Set the internal switch for DO output. This is not displayed if DI-1 was selected for the
DIO type.

• DO Number

Set the DO number to be output. This is not displayed if DI-1 was selected for the
DIO type. If DO-2, DIO-12, DO-2P, or DIO-12P is selected for the DIO type, set the
DO for when the internal switches are ON and for when they are OFF. Set a different
DO number for ON and OFF.
DO numbers may not overlap with other numbers, including DIO operation monitoring
numbers.

4.14 DIO Operation Monitoring Function Settings (Style Number S3 or Later)