10.5 Setting the Rolling Average

This section explains how to set the computed value to the rolling average of the
computed results.

Procedure

Opening the Operation Display

Press the keys in the following sequence:

MENU key

(switch to setting mode(control)) >

MENU key

(switch to Set mode) >

#8

soft key

(select [Math set2(Tag,TLOG,Rolling average,Alarm delay)])

The following display appears.

Operations on the Display

1. Use the

arrow keys

to move the cursor (blue) to the [First-CH] and [Last-CH]

boxes.

2. Press the

soft key

corresponding to the start and end channel numbers for setting

the [Rolling Average].

3. Use the

arrow keys

to move the cursor (blue) to the entry boxes under [Rolling

average].

4. Press the

DISP/ENTER key

.

Setup Items

Setting the Rolling Average

• Off/On

To take the rolling average of the measured results, select [On] (initial value is [Off]).

• Interval

Select the sampling interval when taking the rolling average from the following:
1s, 2s, 3s, 4s, 5s, 6s, 10s, 12s, 15s, 20s, 30s, 1min, 2min, 3min, 4min, 5min, 6min,
10min, 12min, 15min, 20min, 30min, and 1h.
However, if the scan interval is set to [2s], the sampling interval cannot be set to [1s].
In addition, if the scan interval is set to [2s] and the sampling interval is set to an odd-
numbered sampling interval [1s], [3s], [5s], or [15s], the actual sampling interval is set
to [2s], [4s], [6s], or [16s], respectively.

• Number of samples

Set the average count when taking the rolling average using an integer between [1]
and [64].