When checking the control output, set the preset output first (see section 4.9). Then, use
single loop control with the operation stopped.

Is the control output

type set correctly?

NO

NO

NO

NO

YES

YES

YES

YES

Set the current output range or
cycle time* to an appropriate value.

Select the correct output type.

Is the current output

range (during current output)

or cycle time (for time ratio)

setting appropriate?

Is the wiring correct?

Is the output load

appropriate?

Contact your nearest YOKOGAWA

dealer.

See section 4.3.

See section 4.3.

See section 2.3.

* You must wait for the specified cycle

time to elapse before checking.

• Wire correctly.

• Firmly fasten the terminal screws.

Check the output load
condition and set the load correctly.

See section 14.8.

12.2 Troubleshooting Flow Chart