Control output (loop1 to 6) wiring, Contact output (digital out) wiring – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 137

Advertising
background image

2-20

IM 04L31A01-01E

Control Output (LOOP1 to 6) Wiring

C

mA

+

4 to 20 mADC or
0 to 20 mADC

Voltage pulse output

Current output

Relay contact output

C

PULS

250 VAC, 3 A or
30 VDC, 3 A
(resistive load)

Voltage pulse (12 V)

(when set to energized)

+

NC

C

NO

Current Output Specifications
Output signal:

4 to 20 mADC or 0 to 20 mADC

Load resistance: 600 Ω or less
Voltage Pulse Output Specifications
Output signal:

ON voltage = 12 VDC

Load resistance: 600 Ω or more
Relay Contact Output Specifications
Output signal:

NC, NO, COM

Contact rating:

250 VAC (50/60 Hz)/3 A or 30 VDC/3 A (resistive load)

Contact Output (DIGITAL OUT) Wiring

Relay contact output of the control output terminal block

C

NO

250 VAC, 1 A or
30 VDC, 1 A
(resistive load)

Transistor output of the control output terminal block

C

6

5

4

3

24 VDC/50 mA

Transistor output of the control expansion DIO terminal block

4

3

2

1

24 VDC/50 mA

6

5

C

C

12

11

C

3 to 6
1 to 12

+

Pull-up resistor

Connection example

for a transistor output

Relay Output Specifications
Output format:

Relay contact

Contact rating:

250 VAC (50/60 Hz)/1 A or 30 VDC/1 A (resistive load)

Transistor Output Specifications
Output format:

Open collector output

Contact rating:

24 VDC/50 mA

2.3 Wiring

Advertising