Execution errors – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 333

Advertising
background image

12-2

IM 04L31A01-01E

Code

Message

Explanation/Countermeasures/Ref. section

92

Press [ESC] key to change to operation mode.

Press the ESC key.

93

String including space or all space cannot be specified.

Spaces are not allowed in the Web browser user
name and password.

94

More than one address cannot be specified.

Only a single sender is allowed.

100

IP address doesn’t belong to class A, B, or C.

See the Communication Interface User’s Manual.

101

The result of the masked IP address is all 0s or 1s.

See the Communication Interface User’s Manual.

102

SUBNET mask is incorrect.

See the Communication Interface User’s Manual.

103

The net part of default gateway is not equal to that of IP address.

See the Communication Interface User’s Manual.

104

FTP client failed because the memory mode is ‘manual’.

See the Communication Interface User’s Manual.

120

The start segment number is greater than the end segment number. See section 5.6.

121

The On-time is greater than the Off-time.

See section 5.5.

122

Exceeded the number of events which can be set.

See section 5.5.

130

The lower span limit is greater than the upper span limit.

See section 4.6.

131

The range of the span is wider than 30000.

See section 4.6.

132

The lower scale limit is greater than the upper scale limit.

See section 4.6.

133

The range of the scale is wider than 30000.

See section 4.6.

134

The lower and upper span limits of the PV range are equal.

See section 4.6.

135

The lower span limit of the PV range is greater than the upper

See section 4.6.

span limit.

136

The range of the PV range is wider than 30000.

See section 4.6.

137

The lower span limit of the PV switching exceeds the PV range.

See section 4.6.

138

The upper span limit of the PV switching exceeds the PV range.

See section 4.6.

139

The lower and upper span limits of the PV switching are equal.

See section 4.6.

140

The lower span limit of the PV switching is greater than the upper

See section 4.6.

span limit.

141

The lower and upper limits of the output are equal.

See section 4.9.

142

The lower limit of the output is greater than the upper limit.

See section 4.9.

143

The lower and upper limits of the target setpoint are equal.

See section 4.12.

144

The lower limit of the target setpoint is greater than the upper limit.

See section 4.12.

145

The setting of the reference point is incorrect.(n.RP > n+1.RP)

See section 4.8.

146

Incorrect input I/O data. (Set point number <> 2)

See section 4.11.

147

Incorrect input I/O data. (Output(n-1) > Output(n))

See section 4.11.

148

Incorrect input I/O data. Input+Output exceeds the range.

See section 4.11.

149

Incorrect input I/O data. (Input+Output(n-1) > Input+Output(n))

See section 4.11.

• Execution Errors

Code

Message

Explanation/Countermeasures/Ref. section

150

This action is not possible because sampling is in progress.

See section 9.1.

151

This action is not possible during sampling, calculating or controlling. See section 9.1.

152

This action is not possible because saving is in progress.

Wait until the saving ends.

153

This action is not possible because formatting is in progress.

Wait until the formatting ends.

155

The message is not written while sampling is stopped.

See sections 8.9 and 9.1.

160

Cannot load the specified data. Change the memory setting.

See section 9.3.

165

Auto setting is not possible becase the target is not support.

Use manual setting instead of auto setting.
See the Communication Interface User’s Manual.

166

This action is not possible because communication protocol is not

Set the communication setting to “Master.”

“Modbus-M”.

(See the Communication Interface User’s Manual.)

12.1 Messages