6 program parameter setting > event setting, Program parameter setting > event setting -8 – Yokogawa Data Acquisition with PID Control CX2000 User Manual

Page 217

Advertising
background image

5-8

IM 04L31A01-01E

5.6

Program parameter setting > Event setting

This section explains the procedures for setting the events during program control.

Procedure

Opening the Setting Display

Press the keys in the following sequence:

MENU key

(switch to the setting mode (control)) >

#7 soft key

(select [Program-

control parameters]) >

#1 soft key

(select [Program parameter setting])>

#5 soft

key

(select [Event setting])

Move to the program pattern setting display

Increment/Decrement the segment number

Setup Procedure

1. Use the

arrow keys

to move the cursor (blue) to the item box you wish to change.

A soft key menu is displayed at the bottom of the display.

2. Press the

soft key

corresponding to the value you wish to select.

The box for the item you changed turns yellow, and the cursor moves to the next
item.

3. Repeat steps 1 and 2 to change the value of all the items you wish to change.
4. Press the

DISP/ENTER key

to confirm the changes.

The boxes for the items you changed turn from yellow to white, and the cursor
returns to the first item box.

Setup Items

Event setting

• Pattern number

Displays the pattern number selected in the pattern initial settings.

• Segment number

Set the segment number [1] to [99] to which the event is to be assigned.

• Event kind

Select the type of event to be assigned, [PVEvent] or [TimeEvent].

• 1 to 16

The time event or PV event number. The number of time events and PV events that
can be set per segment is 16 each.